background image

- 14 -

2. GENERAL

Gas-fired warm air heater (WAH) for commercial
and industrial applications. The
NG-15 series as semi-automatic unit with piezo-
ignition and thermoelectrical flame control or the
NG-35 to NG-100 as a fully-automatic device with
electrical ignition and ionization monitoring.

3. SAFETY FEATURES

3.1 NG-15 Safety Features

The WAH is equipped with a safety temperature
controller (Item 3) as a safety feature to prevent
overheating.

The thermo-switch shuts down the WAH upon
exceeding the defined temperature.

After cool-down of the WAH the cause must first
be eliminated and the WAH must then be
restarted manually (see “Initial operation and
further start-ups”, page 15).

The WAH is equipped with a thermoelectric flame
failure control for flame monitoring (Item 5).
When the flame extinguishes, gas supply is
immediately interrupted.

3.2 NG-35 - NG-100 Safety Features

The WAH is equipped with a safety temperature
controller (STC) as a safety feature to prevent
overheating. (Item 15 )

The STC shuts down the WAH upon exceeding
the defined temperature.
The integrated restart lock prevents restarting of
the device.

After cooling the WAH, the cause must be
eliminated and the STC must be manually
released. The reset button is located on the
control box under the black screw cap (Item 24).
Then press the release button for the automatic
gas-firing device on the front panel of the
switching box (Item 16).

The built-in ionization electrode serves as a flame-
monitoring device and is connected to the
automatic gas-firing unit that controls and
monitors the overall function of the WAH.

4. INSTALLATION/ ASSEMBLY

In order to prevent personal injury and
property damage, the relevant local building,
fire-prevention and professional
organizational regulations must be
unconditionally observed.

Before setting up it must be ensured that the
local supply conditions (gas type, pressure)
and the current setting of the WAH
correspond.

The WAH may be operated only in well-ventilated
spaces and must 

not

 be used in residential or

similar premises.

To comply with the MAC limit values at the set-up
location, for each KW of device output a fresh air
exchange rate of at least 25 m

3

/h must be

ensured.

Operation in environments at risk of fire or
explosion is 

prohibited

.

The WAH is set up freely in the room on a level
surface without a chimney connection.

The distance from combustible parts must be at
least 1.5 m ,, on the outlet side of the device at
least 3 m.

Any attachment of pipes, hoses or the like as well
as changes to the cross-section is 

prohibited

 on

the inlet and outlet side.

Caution!!!

WAH electrical and gas hookups must be
done only by a specialist and in accordance
with local standards.

Electrical Connection

The electrical connection is made using a built-in
power cable with three-wire grounded plug to a
230 V / 50 Hz a.c. power line.

Gas Hook-up

3/8" external thread with inner cone (note left-
hand thread) on the device.

The WAH can be equipped with a 3.0 m long gas
hose, hose break protection and a corresponding
pressure regulator with combination bottle
connection thread as accessories. The connection
to the gas lines must be made using appropriate
connectors (note left-hand thread).

Summary of Contents for NG-100

Page 1: ...0 Betriebsanleitung Operating Instructions Mode d utilisation NG 15 35 50 75 100 Gustav Nolting GmbH Neuzeitliche Heiztechnik...

Page 2: ...stellung Montage Seite 3 4 5 Inbetriebnahme Seite 4 6 Ausserbetriebnahme Seite 4 7 Wartungsarbeiten Seite 4 8 M gliche St rungen und deren Ursachen Seite 5 9 Ersatzteillisten und Bauteile bersicht Sei...

Page 3: ...druck bar 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 Anschlu wert kg h 0 54 1 09 1 41 2 73 1 95 3 91 2 73 5 47 3 91 7 81 Stromaufnahme A 0 48 0 48 0 48 0 60 0 92 L nge mm 500 500 650 800 1 000 Breit...

Page 4: ...onisationselektrode dient als Flammen berwachung und ist an einen Gas feuerungsautomaten angeschlossen der die Gesamtfunktion des WLE steuert und berwacht 4 AUFSTELLUNG MONTAGE Um Personen und Sachsch...

Page 5: ...ebungstemperatur einge stellt werden Mit dem Ventilator wird die Z ndung automatisch eingeschaltet und nach einer kurzen Vorsp lzeit das Magnetventil Pos 9 ge ffnet Nach der Flammenbildung wird die Z...

Page 6: ...lt zu gro Z ndkabel defekt Pos 7 Gasfeuerungsautomat defekt Pos 16 Austauschen Verkleinern Austauschen Austauschen WLE l uft an Z ndung ist vor handen Magnetventil ffnet Gas str mt ein wird entz ndet...

Page 7: ...11 Thermostromunterbrecher 102814 12 Z ndelektrode 103314 103312 103312 103311 103311 13 Piezoz nder 103315 14 Ger teregler 103040 103040 103040 103040 103040 15 Sicherheitstemperaturbegrenzer STB 100...

Page 8: ...7 NG 15 35 50...

Page 9: ...8 NG 75 100...

Page 10: ...9 11 ELEKTRISCHER SCHALTPLAN Ger tetyp NG 15...

Page 11: ...10 11 ELEKTRISCHER SCHALTPLAN Ger tetyp NG 35 50...

Page 12: ...11 11 ELEKTRISCHER SCHALTPLAN Ger tetyp NG 75 100...

Page 13: ...sembly Page 14 15 5 Initial operation and further start ups Page 15 6 Placing out of service Page 15 7 Maintenance Page 15 8 Possible malfunctions and their causes Page 16 9 Spare Parts List and Compo...

Page 14: ...on pressure bar 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 Connected load kg h 0 54 1 09 1 41 2 73 1 95 3 91 2 73 5 47 3 91 7 81 Power consumption A 0 48 0 48 0 48 0 60 0 92 Length mm 500 500 650 80...

Page 15: ...he automatic gas firing unit that controls and monitors the overall function of the WAH 4 INSTALLATION ASSEMBLY In order to prevent personal injury and property damage the relevant local building fire...

Page 16: ...om thermostat the thermostat must be set using room temperature With fan ignition is automatically turned on and after a short pre purge time the solenoid Item 9 is opened After establishing the flame...

Page 17: ...nition gap too large Ignition cable defective Item 7 Automatic gas firing unit defective Item 16 Replace Reduce Replace Replace WAH starts ignition present solenoid valve opens gas flows in is ignited...

Page 18: ...l 102661 102389 102389 11 Thermo circuit breaker 102814 12 Ignition electrode 103314 103312 103312 103311 103311 13 Piezo igniter 103315 14 Device controller 103040 103040 103040 103040 103040 15 Safe...

Page 19: ...18 NG 15 35 50...

Page 20: ...19 NG 75 100...

Page 21: ...20 11 ELECTRICAL CIRCUIT DIAGRAM Device Type NG 15...

Page 22: ...21 11 ELECTRICAL CIRCUIT DIAGRAM Device Type NG 35 50...

Page 23: ...22 11 ELECTRICAL CIRCUIT DIAGRAM Device Type NG 75 100...

Page 24: ...llation Assemblage Pages 25 26 5 Mise sous tension Page 26 6 Mise hors tension Page 26 7 Maintenance Page 26 8 Les dysfonctionnements possibles et leurs causes Page 27 9 Liste des pi ces de rechange e...

Page 25: ...n du gaz l entr e bar 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 D bit de gaz kg h 0 54 1 09 1 41 2 73 1 95 3 91 2 73 5 47 3 91 7 81 Consommation de courant A 0 48 0 48 0 48 0 60 0 92 Longueur mm 50...

Page 26: ...er des dommages personnels et mat riels les r gulations en vigueur relatives la construction la protection contre les incendies ainsi que les stipulations des associations professionnelles sont respec...

Page 27: ...p rature ambiante L allumage est enclench en m me temps que le ventilateur et apr s un bref d lai de pr rin age la vanne lectromagn tique s ouvre pos 9 Lorsque la flamme est allum e l allumage s teint...

Page 28: ...trop grande C ble d allumage d fectueux pos 7 Br leur gaz automatique d fectueux pos 16 Remplacez R duisez Remplacez Remplacez Le GAC d marre l allumage s enclenche la vanne lectromagn tique s ouvre l...

Page 29: ...Disjoncteur de courant thermo lectrique 102814 12 Electrode d allumage 103314 103312 103312 103311 103311 13 Pi zoallumage 103315 14 R glage de l appareil 103040 103040 103040 103040 103040 15 Limitat...

Page 30: ...29 NG 15 35 50...

Page 31: ...30 NG 75 100...

Page 32: ...31 11 SCHEMA DES CONNEXIONS ELECTRIQUES Type d appareil NG 15...

Page 33: ...32 11 SCHEMA DES CONNEXIONS ELECTRIQUES Type d appareil NG 35 50...

Page 34: ...33 11 SCHEMA DES CONNEXIONS ELECTRIQUES Type d appareil NG 75 100...

Page 35: ...derger tebau Blechbearbeitung Our Comprehensive Supply Program Warm Air Heaters System Construction Air Ducts Fans for air supported domes and other flexible structures Control Systems Construction Li...

Reviews: