6K V1.02 03-16-91
127
POWER ON
EVENT-TRIGGERED MACRO
Command Form:
(PW) 26 00 (macro name) *
Description:
This command assigns a macro to be executed when the controller goes
through a warm start up. Enter a 4-digit macro name, using leading zeroes it
the macro name is less than 4 digits long. To delete the assignment, enter
no macro name.
Acknowledgement:
OK
Errors:
? ERR 1
wrong number of digits entered
? ERR 2
illegal digit entered
Default Condition:
no macro is assigned
Examples:
This command is useful for initializing hardware at the repeater site following
a power interruption. A macro can be created that momentarily switches on
the logical outputs; this macro is then triggered by a restart.
The command has no effect after a cold restart, since all macros are deleted
anyway.
As an example of how this command may be used, assume that macro
3456* has been created to change the CW frequency to a high pitch. To
arrange triggering of this macro from a restart, enter:
(PW) 26 00 3456 *
If power at the repeater site should fail and return later, the controller will
notify you since the CW pitch is now higher. You may enter a macro or a
control command that changes the CW pitch back to normal, awaiting the
next power "glitch".