2. TERMINAL
2. TERMINAL
DESCRIPTION
DESCRIPTION
2.2 FRONT PANEL LEDS
2.2 FRONT PANEL LEDS
•
Five Leds used to indicate the operating mode.
•
Seven input Leds used to indicate the status of the inputs.
2.3 STATUS AND FAULTS
2.3 STATUS AND FAULTS
2.3.1 GENSET STATUSES
2.3.1 GENSET STATUSES
Status Display
Abbreviation
Standby ( Not ready)
Standby
Standby
Ready
Ready Ready
Coun ng Response delay to give start order
Response
RSP
Start order is given (ST.Gx engaged)
Star ng Star ng
Gx OK signal active with No AC signals from genset
OK-Wai ngAC
OK-NoAC
Coun ng Warm-up delay to engage load
Warm Up
WUp
Engaging load (CGx Engaged) with No CGx F/B detected yet
Engaging
Engaging
Load engaged (CGx Engaged with CGx F/B detected) with No CG F/B
detected yet
Engaged Engaged
Feeding the load (CGx Engaged with CGx F/B & CG F/B detected )
Feeding Load
Feeding
Disengaging the load (CGx Disengaged) with CGx and/or CG F/B s ll
detected
Disengaging Diseng.
Coun ng Cooling delay to disengage start order
Cooling
COL
Shu ing down ( Start order released)
Shut ng SDN
2.3.2 GENSET FAULTS
2.3.2 GENSET FAULTS
Fault
Display Abbrevia on
Start Fail caused by absence of Gx OK signal
StFail-NoOK
StF.NoOK
Start Fail caused by Failure of G contactor
StFail-CG-F StF.CG-F
Start Fail caused by Failure of Gx contactor
StFailCGx-F
StF.CGxF
Start Fail caused by Absence of AC signals
StFail-NoAC StF.NoAC
Start Fail caused by High voltage
StFail-HiV.
StF.HiV
Start Fail caused by Low voltage
StFail-LoV. StF.LoV
Start Fail caused by High frequency
StFail-HiF.
StF.HiF
Start Fail caused by Low frequency
StFail-LoF. StF.LoF
Start Fail caused by wrong phase sequence
StFail-Seq-F
StF.Seq
Start Fail caused by G contactor jam
StFail-CGJam StF.CG-J
Start Fail caused by Mains contactor jam
StFail-CMJam
StF.CM-J
Start Fail caused by the other generator contactor jam
StFail-CGyJam StF.CGyJ
Start Fail caused by the expire of start failure delay
StFail-Time
StF.Time
Gx OK Signal lost a er generator has turned on
OK Failure
OK Fail
Global contactor failure
CG Fail
CG Fail
CGx Contactor failure
CGx Fail
CGx Fail
One of the three-phase voltages goes above the over voltage limits set by
OVolt(L-N) for a delay of OVolt del.
Hi Voltage
Hi Volt.
One of the three-phase voltages goes below the under voltage limits set by
UVolt(L-N) for a delay of UVolt del.
Lo Voltage
Lo Volt.
The frequency goes above the value set in Over Freq. for a delay of OFreq
del.
Hi Freq.
Hi Freq.
The frequency goes below the value set in Under Freq. for a delay of UFreq
del.
Lo Freq.
Lo Freq.
The phases are reversed
Wrong Seq.
Seq.Fail
The load exceeds the value set by Overload % for a delay of Overld del
Over Load
Over Ld.