Start Fail
Start fail delay
N/A
(Warm up +Transfer dead me+10) to
999 sec
45 sec
Hold Start
Hold Start feature
Client P/W
N: Start order released a er start
failure
Y: Start order held a er start failure
Time Switch
Time Switch opera on N/A
N: Opera on disabled
Y: Opera on enabled
N
Ready @
Gensets ready at me
“Time Switch”
set to Y
N/A
8:00 AM
Stdby @
Gensets standby at
me
“Time Switch”
set to Y
N/A
5:00 PM
All Days Ready
Gensets ready feature
N/A
N: Have to set the gensets ready days
Y: Gensets ready all days of the week
Y
Sunday
Gensets readiness on
Sunday
“All Days Ready”
set to N
N: Genset not ready on Sunday
Y: Genset ready on Sunday
N
Monday
Gensets readiness on
Monday
“All Days Ready”
set to N
N: Genset not ready on Monday
N
Tuesday
Gensets readiness on
Tuesday
“All Days Ready”
set to N
Y: Genset ready on Tuesday
N
Wednesday
Gensets readiness on
Wednesday
“All Days Ready”
set to N
N: Genset not ready on Wednesday
N
Thursday
Gensets readiness on
Thursday
“All Days Ready”
set to N
Y: Genset ready on Thursday
N
Friday
Gensets readiness on
Friday
“All Days Ready”
set to N
N: Genset not ready on Friday
N
Saturday
Gensets readiness on
Saturday
“All Days Ready”
set to N
Y: Genset ready on Saturday
N
Weekly Ex.
Weekly Exercising
N/A
N/Y
N
Alternate hrs
Alternate number of
hours
“Omega Type”
set to ATS
G1: Highest priority to G1
G2: Highest priority to G2
1 to 99 hours
4 hours
Req Priority
Request Priority
“Omega Type”
set to ATSO
G1: Highest priority to G1
G2: Highest priority to G2
Ld (MGG only): Load dependent
priority
G2
G1 hours
G1 running hours
Client P/W
0 to 999999 hours
0 hours
G2 hours
G2 running hours
“Inst. Type”
set to MGG or
GG
Client P/W
0 to 999999 hours
0 hours
R.C.
Remote control
con
fi
gura on
N/A
Gensets Rdy: Gensets are ready
U Present: Simulate u lity presence
v1.0 Compt.: Compa ble with Omega
v1.0
U Present
NB Phases
Gensets connec on
N/A
1PH: 1 phase
3PH: 3 phases
3PH
CT ra o /5
Current transformer
ra o
N/A
N, 1 to 9999
100
Overload %
Gensets Overload % of
the current transformer
“Omega Type”
set to ATS
0 to 100%
90%
Overld del
Gensets Overload delay
“Omega Type”
set to ATS
0 to 999 seconds
10
G1 Overload %
G1 Overload % of the
current transformer
“Omega Type”
set to ATSO
0 to 100%
90
G1 Overld del
G1 Overload delay
“Omega Type”
set to ATSO
0 to 999 seconds
10
What you see on the
display
Descrip on
Visibility Condition
Range
Default Value
2. TERMINAL
2. TERMINAL
DESCRIPTION
DESCRIPTION
13