KEY FUNCTIONS

 

 

The

 

A = ON/OFF KEY - When the Z2000RT is not locked, this 

key allows the thermostat to be turned ON or OFF. When in the 
OFF position, the damper is also driven closed. 
 
B = STATUS KEY - Pressing the STATUS key displays the 
UNIT number, ZONE number, DUCT temperature and 
DAMPER position. 
 
C and D = UP and DOWN KEYS - These keys are used to 
increase or decrease the setpoint as well as change thermostat 
setup values. 
 
E = SETUP KEY - This key is used to toggle through the 
thermostat 
setup menu. 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

 
 
 

 
 
 
 
 
 

ATTACHING THE THERMOSTST TO THE SUB-BASE 

 
When attaching the thermostat to the sub-base, first place the 
hinged access cover on by fitting the plastic molded pins into 
the grooves at the top of the thermostat. Carefully align the two 
standoffs located at the top of the thermostat with the slots in 
the top of the sub-base. Allow the thermostat to swing 
downward and gently push until the connector pins are fully 
seated into the terminal blocks. 
 

 
 
 

 

THERMOSTAT SETUP

 

Apply 24 Volts power to the thermostat. The LCD Display  
will momentarily display all icons as shown in Figure 1.  

 

 

 

 

ENTERING THE SETUP MENU

 

Press twice and hold the SETUP key until the word DAMPER  
appears on the LCD screen as indicated on Figure 2. 

 

SETTING THE MINIMUM DAMPER POSITION 

Press the SETUP key again and the LCD will 
display the minimum damper position. The factory  
default is 10% which means the damper is driven  
90% closed after a heating or cooling call is satisfied.  
Press the UP and DOWN keys to change the minimum  
damper position. Position may be adjusted in  
10% increments (see Figure 3). 

 

SETTING THE MAXIMUM DAMPER POSITION 

Press the SETUP key again and the LCD will display 
the maximum damper position for heating and cooling.  
The factory default is 100% which means the damper  
can drive fully open with a call for heating or cooling.  
Position may be adjusted in 10% increments using the 
UP and DOWN keys as shown in Figure 4. 

 
SETTING A UNIT NUMBER 

Press the SETUP key again and the LCD will display  
the word UNIT. The factory default is 00. This number 
can be used to assign the Z2000RT to a particular  
HVAC unit. Use the UP and DOWN keys to assign a 
UNIT number from 00 to 99. (Figure 5) 
 
 
 
 

Summary of Contents for Z2000RT

Page 1: ...one Control Solutions Installation Maintenance Manual Model Z2000RT Wall Mount Thermostat II Z2000RT 613 New ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE OR OBLIGATION RUSKIN 2013 ...

Page 2: ...sert a small coin in the release slot located on the bottom of the thermostat Gently twist the coin to release the thermostat from the sub base Avoid twisting the case as this may stress the LCD and cause it to crack or bend the terminal pin connectors TERMINAL DESIGNATIONS The Z2000RT has dedicated screw terminals located on the sub base to facilitate ease of wiring to the actuator logic card mou...

Page 3: ...may warp causing improper seating of the thermostat connecting pins to the terminal blocks Use a properly sized screwdriver and terminate each wire to its dedicated terminal Do not over tighten the terminal screws Check to see that all wires are landed correctly and dressed properly to prevent any shorts SWITCH FUNCTIONS The Z2000RT contains a set of dip switches numbered 1 through 8 Only dip swit...

Page 4: ...lone Modulating Damper or Diffuser System Z2000 Modulating Zone Control System 4 WIRE TO OPTIONAL TRACER DSAMPER S UP TO 20 MAY BE WIRED IN PARALLEL Z2000RT WIRE TO OPTIONAL TRACER DAMPER S UP TO 20 MAY BE WIRED IN PARALLEL Z2000RT ...

Page 5: ...to the thermostat The LCD Display will momentarily display all icons as shown in Figure 1 ENTERING THE SETUP MENU Press twice and hold the SETUP key until the word DAMPER appears on the LCD screen as indicated on Figure 2 SETTING THE MINIMUM DAMPER POSITION Press the SETUP key again and the LCD will display the minimum damper position The factory default is 10 which means the damper is driven 90 c...

Page 6: ...amper blade fully open or fully closed This is a critical step in the Z2000RT setup since the thermostat can be used with a variety of 24 Volt actuators If you are unsure of the actuator speed place the actuator in the fully closed position and then apply 24 Volts to common and normally open The time it takes to drive the damper blade fully open equals the actuator speed setting Figure 9 SETTING T...

Page 7: ... status points UNIT Displays the HVAC unit number assigned to thermostat ZONE Displays the thermostat zone number DUCT Displays the duct temperature DAMPER Displays the damper position in one degree increments 0 fully closed and 100 fully open THERMOSTAT OPERATION The Z2000RT is designed to provide accurate but simple temperature control for the user When the thermostat is not calling only the spa...

Page 8: ...ng Temperature 23 F to 122 F Operating RH 0 95 non condensing Size 4 7 16 W x 4 1 16 H x 7 8 D LCD Display Size 2 3 4 W x 1 7 8 H Temperature Sensor 10K NTC type 3 Accuracy 1 F 77 F Display Resolution 1 F Control Range 36 F to 96 F Back Light Blue EL Electro Luminescent Back Light Life 3 000 hours to half brightness Communications Protocol Modbus Approvals FCC Part 15 Pending C tick Warranty 5 yea...

Reviews: