SETTING A ZONE NUMBER 

Press the SETUP key again and the LCD will display 
the word ZONE. The factory default is 00. This number  
can be used to identify each Z2000RT thermostat wired 
to a Z2000 zone control panel or when used in multiple  
stand-alone applications. Use the UP and DOWN keys 
to assign a ZONE number from 00 to 99. (Figure 6) 

 

SETTING THE HEATING LIMIT  

Press the SETUP key again and the LCD will display  
the heating limit. The factory default is 76° F. Press the 
UP and DOWN keys to change the heating limit setting. 
It is strongly recommended that the limit not be set  
Above Thefactory default setting. (Figure 7) 

 
SETTING THE COOLING LIMIT  

Press the SETUP key again and the LCD will display 
the cooling limit. The factory default is 68° F. Press 
the UP keys to change the cooling

 

limit setting. It is  

strongly recommended that the limit not be set below 
the factory default setting.  Refer to Figure 8. 

 

SETTING THE ACTUATOR SPEED 

Press the SETUP key again and the LCD will display 
the actuator speed. The factory default is 90 seconds  
which is the time it takes the actuator to drive the  
damper blade fully open or fully closed. This is a critical 
step in the Z2000RT setup since the thermostat can 
 be used with a variety of 24 Volt actuators. If you are 
unsure of the actuator speed, place the actuator in the 
fully closed position and then apply 24 Volts to common 
and normally open. The time it takes to drive the damper 
blade fully open equals the actuator speed setting. 
(Figure 9) 

 
SETTING THE MODBUS ADDRESS 

Press the SETUP key again and the LCD will display 
the Modbus communications address. The factory 
default is 01. The Z2000RT has integrated Modbus 
communications capability for remote monitoring  
and control. For more information on Modus  
Communications, contact Ruskin (Figure 10). 

 

TEMPERATURE CALIBRATION OFFSET 

Press the SETUP key again and the LCD will display 
the temperature calibration offset as shown on  
Figure 11. The factory default setting is 0. Typically, 
it is not necessary to adjust the temperature calibration 
 offset as the Z2000RT has been factory calibrated. 
If calibration is necessary, a high quality electronic  
digital thermometer must be used. Place the  
thermometer sensor probe next to the thermostat  
sensor and allow five minutes before comparing 
the temperature readings. Use the UP and 
DOWN keys to adjust the temperature calibration. 
The range is +/- 9° F. 

 
 
 
 
 
 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Z2000RT

Page 1: ...one Control Solutions Installation Maintenance Manual Model Z2000RT Wall Mount Thermostat II Z2000RT 613 New ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE OR OBLIGATION RUSKIN 2013 ...

Page 2: ...sert a small coin in the release slot located on the bottom of the thermostat Gently twist the coin to release the thermostat from the sub base Avoid twisting the case as this may stress the LCD and cause it to crack or bend the terminal pin connectors TERMINAL DESIGNATIONS The Z2000RT has dedicated screw terminals located on the sub base to facilitate ease of wiring to the actuator logic card mou...

Page 3: ...may warp causing improper seating of the thermostat connecting pins to the terminal blocks Use a properly sized screwdriver and terminate each wire to its dedicated terminal Do not over tighten the terminal screws Check to see that all wires are landed correctly and dressed properly to prevent any shorts SWITCH FUNCTIONS The Z2000RT contains a set of dip switches numbered 1 through 8 Only dip swit...

Page 4: ...lone Modulating Damper or Diffuser System Z2000 Modulating Zone Control System 4 WIRE TO OPTIONAL TRACER DSAMPER S UP TO 20 MAY BE WIRED IN PARALLEL Z2000RT WIRE TO OPTIONAL TRACER DAMPER S UP TO 20 MAY BE WIRED IN PARALLEL Z2000RT ...

Page 5: ...to the thermostat The LCD Display will momentarily display all icons as shown in Figure 1 ENTERING THE SETUP MENU Press twice and hold the SETUP key until the word DAMPER appears on the LCD screen as indicated on Figure 2 SETTING THE MINIMUM DAMPER POSITION Press the SETUP key again and the LCD will display the minimum damper position The factory default is 10 which means the damper is driven 90 c...

Page 6: ...amper blade fully open or fully closed This is a critical step in the Z2000RT setup since the thermostat can be used with a variety of 24 Volt actuators If you are unsure of the actuator speed place the actuator in the fully closed position and then apply 24 Volts to common and normally open The time it takes to drive the damper blade fully open equals the actuator speed setting Figure 9 SETTING T...

Page 7: ... status points UNIT Displays the HVAC unit number assigned to thermostat ZONE Displays the thermostat zone number DUCT Displays the duct temperature DAMPER Displays the damper position in one degree increments 0 fully closed and 100 fully open THERMOSTAT OPERATION The Z2000RT is designed to provide accurate but simple temperature control for the user When the thermostat is not calling only the spa...

Page 8: ...ng Temperature 23 F to 122 F Operating RH 0 95 non condensing Size 4 7 16 W x 4 1 16 H x 7 8 D LCD Display Size 2 3 4 W x 1 7 8 H Temperature Sensor 10K NTC type 3 Accuracy 1 F 77 F Display Resolution 1 F Control Range 36 F to 96 F Back Light Blue EL Electro Luminescent Back Light Life 3 000 hours to half brightness Communications Protocol Modbus Approvals FCC Part 15 Pending C tick Warranty 5 yea...

Reviews: