43
English
Status and control word, protocol address 33
Function
Authority
Comment
Bit 0
1 = Error present
R
Bit 1
1 = Pre-heating mode
R
Bit 2 Reserved
R
Bit 3 Reserved
Bit 4 Filter changed
R/W
With rising slope, filter change acknowledged
Bit 5
1 = Cancel error
R/W
With rising slope, error is cancelled
Bit 6
0 = Unit switched ON
1 = Unit switched OFF
R/W
shut-off with increasing flank
Bit 7
1 = Unit switched ON
0 = Unit switched OFF
R/W
With rising slope, unit switched ON
Bit 8 E-heating module 1
R
1 = present 0 = not present
Bit 9 E-heating module 2
R
1 = present 0 = not present
Bit 10 Reserved
R/W
Bit 11 Reserved
R/W
Bit 12 Reserved
R/W
Bit 13 Reserved
R/W
Bit 14 Reserved
R/W
Bit 15 Reserved
R/W
Register
address Parameter name
Value range
ROTO K 1050 V ROTO K 1700 V ROTO K 2800 V ROTO K 4200 V ROTO K 7600 V
40016
Minimum ventilation supply air
500 - 1400 m³/h
500 - 2000 m³/h
700 - 3200 m³/h
1200 - 6200 m³/h
40017
Minimum ventilation extract air
500 - 1400 m³/h
500 - 2000 m³/h
700 - 3200 m³/h
1200 - 6200 m³/h
40018
Basic ventilation supply air
500 - 1400 m³/h
500 - 2000 m³/h
700 - 3200 m³/h
1200 - 6200 m³/h
40019
Basic ventilation extract air
500 - 1400 m³/h
500 - 2000 m³/h
700 - 3200 m³/h
1200 - 6200 m³/h
40020
Intermittent ventilation supply air
500 - 1400 m³/h
500 - 2000 m³/h
700 - 3200 m³/h
1200 - 6200 m³/h
40029
Intermittent ventilation extract air 500 - 1400 m³/h
500 - 2000 m³/h
700 - 3200 m³/h
1200 - 6200 m³/h
coming soon