9.8. Menu level Commissionning ROTO K
P 1 Minimum set-point value
The parameter P1 shows the lowest setpoint temperature which you may set with the control unit.
Values between 16 °C and 20 °C can be selected. The default setting is 16 °C.
P 2 Maximum set-point value
The parameter P2 shows the highest setpoint temperature which you may set with the control unit.
Values between 20 °C and 30 °C can be selected. The default setting is 22 °C.
P 3 Enable
Switching the unit on and off with an external contact
The unit must be switched on at the control unit.
Contact open. The unit is switched off.
Contact closed. The unit is switched on / ready for operation.
The unit can only be switched on if the contact is closed. If the contact
is open, the display will show „NOT ENABLE“. The contact has to be
closed and at the end confirmed by selecting „OK“.
The default mode is AUTOMATIC.
You can access the parameter settings by selecting the „Settings“ icon. The selection menu will then
appear on the display.
It is necessary to provide a password. This will remain valid for 30 min. After 30 minutes it is neces
-
sary to retype the password in order to continue making changes.
Password: 0213 (is shown as XXX near the time)
You must now select again „Commissioning parameters“.
The display then changes to „P 1 MIN-VALUE“.
The individual menu points may be queried with the icons „▲“ and „▼“. By selecting the values
(shown hachured here) you may activate them (shown in grey) and afterwards you can change the
values with „▲“ and „▼“. You can go back to the Operating display by touching „OK“.
Selection menu
Next you enter the Commissioning level by selecting the icon „Commissioning parameters“.