Function code
Name Sub-function Description
08 Hex
Return Query Dat
00
Send the received message back
08 Hex
Restart Communications
01
Restart communication
08 Hex
Force Listen Only Mode
04
Switch to listen-only mode
13.3.4.
Parameter table
Register
address
Protocol
address
Parameter name
Value range
D a t a
type
Autho-
rity
40001
0
Reserved
integer
R/W
40002
1
Min. set-point value
10 - 500 PA
integer
R/W
40003
2
Max. set-point value
100 - 999 PA
integer
R/W
40004
3
P - component
5 - 15
integer
R/W
40005
4
Pressure correction
-20 - 20 PA
integer
R/W
40006
5
Reserved
integer
R/W
40007
6
Reserved
integer
R/W
40008
7
Reserved
integer
R/W
40009
8
Reserved
integer
R/W
40010
9
Reserved
integer
R/W
40011
10
Set-point: day
Pressure (PA)
integer
R/W
40012
11
Set-point: night
Pressure (PA)
integer
R/W
40013
12
day/night switching
0 = Day-time operation 1 = Night-time
operation
integer
R/W
40034
33
Status and control word
See Table below
integer
R/W
40036
35
Save parameters
12439 Value change after saving under 0 integer
R/W
Function
Authority
Comment
Bit 0
1 = Error present
R
integer
Bit 1
Reserved
R/W
Bit 2
Reserved
R/W
Bit 3
Reserved
R/W
Bit 4
Reserved
R/W
Bit 5
1 = Cancel error
R/W
With rising slope, error is cancelled
Bit 6
0 = Unit switched ON
1 = Unit switched OFF
R/W
shut-off with increasing flank
Bit 7
0 = Unit switched ON
1 = Unit switched OFF
R/W
With rising slope, unit switched ON
Bit 8
Reserved
R/W
Bit 9
Reserved
R/W
Bit 10
Reserved
R/W
Bit 11
Reserved
R/W
Bit 12
Reserved
R/W
Bit 13
Reserved
R/W
Bit 14
Reserved
R/W
Bit 15
Reserved
R/W