Real Time Automation, Inc.
66
1-800-249-1612
1)
Connected and Running
–
The gateway is connected to all the DF1 slaves.
2)
Error: Timeout
–
No DF1 scan lines are configured under an enabled slave.
a)
Or, one or more enabled DF1 slaves are missing.
b)
Verify DF1 device for correct Destination ID.
c)
Verify that Port Settings used match the DF1 slave(s) that the gateway is communicating with.
d)
Verify wires for specific port settings.
3)
Dependency Protocol Faulted
–
The dependent protocol is missing causing the communication to
stop.
4)
Unknown: First Scan Not Complete
–
Multiple scan lines are set up for the device and the gateway
has not completed all the scan lines for the first time.
5)
Fatal Error: Couldn’t Open Hardware Port –
The serial port selected on the DF1 Master
Configuration page is not configured.
6)
Fatal Error: No Configuration
–
No DF1 slaves are enabled though a serial port is enabled.
LED Status
- This is the status for
All Slaves,
or the specific slave selected.
1)
Solid Green (Connected)
–
The gateway is connected to all the DF1 slaves that are configured and
enabled.
2)
Flashing Green (Not Connected)
–
No DF1 slaves are enabled/configured.
a)
Verify DF1 settings and ensure that the
Enable
checkbox is checked for the appropriate slave(s).
3)
Flashing Red (Connection Timeout) - The gateway cannot open a connection to one or more of the
enabled DF1 devices.
a)
Verify DF1 Communication Command.
b)
Verify DF1 Destination IDs.
c)
Verify port settings used match the DF1 slave that the gateway is communicating with, including
Protocol Mode and Frame Verification.
d)
Verify wires for specific port settings.
4)
Flashing Red (Empty Scan List) - One or more enabled DF1 slaves have no scan lines configured.
5)
Flashing Red (Communication not attempted yet)
–
(Specific slave only) No reads are configured and
data needed for writes isn’t valid yet.
6)
Flashing Red (Dependency Error) - The dependent protocol is missing causing the communication to
go to inactive.
a)
The other protocol must be
Connected
.