PROFIBUS Slave Configuration
The PROFIBUS Slave Configuration page lets you configure multiple input and output slots.
1)
PROFIBUS only supports a total of 244 input bytes and 244 output bytes.
2)
Data Size is configurable. Options include: 2, 4, 8, 16, 24 and 32 bytes.
3)
Data Format sets the formatting of the data. Automap will use this packing size to map data to/from
the other protocol.
There are two ways to configure this protocol:
1)
Auto-Configure Group by Device (Default)
2)
Auto-Configure Group by Data Type
3)
Manual Mode
NOTE
: You may go back and forth between modes, but when reverting from Manual Mode to Auto-
Server Mode, all changes made in Manual Mode will be discarded.