Page 1: ...Mounting and operating instructions SENTERA INTERNET GATEWAY DIG M ...

Page 2: ...ESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 5 VERIFICATION OF THE INSTALLATION INSTRUCTIONS 8 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 DIN RAIL MOUNTED SENTERA INTERNET GATEWAY DIG M ...

Page 3: ...t is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting servic...

Page 4: ... Wi Fi or LAN Ethernet cable DIN rail mounted Enclosure plastic ABS UL94 V0 grey RAL 7035 Protection class IP20 Operating ambient conditions Temperature 10 50 C Rel humidity 5 85 rH non condensing STANDARDS EMC directive 2014 30 EU EN 61000 6 1 2007 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments EN 61000 6 3 2007 E...

Page 5: ...8 1 2 3 4 5 6 7 8 MOUNTING INSTRUCTIONS IN STEPS Before you start mounting the DIG M read carefully Safety and Precautions and follow these steps 1 Slide the unit along the guides of a standard 35 mm DIN rail and fix it to the rail by means of the black locking clip on the enclosure Mind the correct position and mounting dimensions shown in Fig 1 Mounting dimensions and Fig 2 Mounting position Fig...

Page 6: ...cket 4 The DIG M unit needs PoM 24 VDC So either the Slave or Master channel must be powered with 24 VDC ATTENTION Do not connect both circuits with PoM 24 VDC power supply simultaneously Fig 3 Wiring Ethernet PoM Slave PoM Master Top view RJ45 Ethernet connection vt Bottom view RJ45 PoM Modbus RTU and 24 VDC power supply 5 Connect DIG M to the internet via WLAN Wi Fi or LAN Ethernet cable For mor...

Page 7: ...firmware is updated via Modbus RTU communication To enter Boot mode put a jumper onto pins 3 and 4 of the P1 header and restart the power supply see Fig 4 Once Boot mode is activated the firmware can be updated via SM Boot application part of 3SModbus software suite Fig 4 P1 header 1 2 3 4 5 Put a jumper onto pins 1 and 2 and wait for at least 5 seconds to reset the Modbus communication parameters...

Page 8: ...s LED 1 LED 3 LED 2 ATTENTION The status of the LEDs can be checked only when the unit is energised Take the relevant safety measures TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the ...