Device Status
- This will only display when viewing
All Adapters
.
1)
Connected and Running
–
The gateway is connected to all the EtherNet/IP adapters that are enabled
and configured.
2)
Connected and Idle
–
The gateway is connected to all the EtherNet/IP adapters that are enabled and
configured but the configured outputs are not yet valid.
3)
Error: Timeout
–
One or more enabled EtherNet/IP adapters have timeouts.
4)
Fatal Error: No Configuration
–
No EtherNet/IP adapter devices are configured or devices that are
configured are not enabled.
5)
Unknown: First Scan Not Complete
–
I/O Parameters have been configured for an EtherNet/IP
adapter, but a connection has not been established yet.
6)
Dependency Protocol Faulted
–
The dependent protocol is missing causing the communication to go
inactive.
LED Status
- This is the Status for
All Adapters
or the specific Adapter selected.
1)
Solid Green (Connected)
–
The gateway is connected to all the EtherNet/IP adapters that are
configured and enabled.
2)
Solid Green (Connected(Idle))
–
The gateway is connected to all the EtherNet/IP adapters that are
configured and enabled, but the configured outputs are not yet valid.
3)
Flashing Green (Not Connected/First Time Scan)
–
The gateway has never been connected to an
EtherNet/IP adapter that is configured and enabled.
a)
Make sure there are no error codes being returned.
b)
Make sure the adapter device is configured and online.
4)
Flashing Red (Empty Scan List)
–
No EtherNet/IP adapters are configured/enabled.
5)
Flashing Red (Connection Timeout) - One or more enabled EtherNet/IP adapters are timed out or
missing.
a)
Verify that the IP address of each EtherNet/IP adapter is valid and is on the same network as the
gateway.
b)
Verify EtherNet/IP settings and ensure that the
Enable
checkbox is checked for the appropriate
device(s).
c)
Verify the Instance numbers are valid for each EtherNet/IP adapter.
6)
Flashing Red (Dependency Error) - The dependent protocol is missing or has errors causing the
communication to go inactive.
a)
The other protocol must be
Connected
.
7)
Off
–
No Ethernet cable plugged in.