![Rosslare InteliDoor AC-Q41H Instruction Manual Download Page 16](http://html1.mh-extra.com/html/rosslare/intelidoor-ac-q41h/intelidoor-ac-q41h_instruction-manual_1489307016.webp)
Page 30
07/04
between Normal and Secure Mode. By connecting a switch timer to
the auxiliary input you can for example automatically switch the AC-
Q41H from Normal Mode during office hours to secure mode after
office hours.
AUXILIARY MODE 4
In auxiliary mode 4 the AC-Q41H is capable of shunting an alarm
system's door sensor. The auxiliary output should be wired in
parallel to the door sensor. When in use the auxiliary output is
normally open and the door sensor functions normally. When a
valid code is entered the auxiliary relay will shunt the door sensor
for the duration of the shunt time as defined by the auxiliary setting.
If the door is left open longer than the shunt time the alarm will be
triggered.
AUXILIARY MODE 5
In auxiliary mode 5 the AC-Q41H is capable of shunting an alarm
system. In this mode the auxiliary input should be wired to the
magnetic contact switch on the door. The auxiliary relay should be
wired to the alarm system. Without a valid code entered the
auxiliary relay will match the condition of the magnetic contact
switch, if the door opens the auxiliary relay will open, if the door
closes the auxiliary relay will close. When a valid code is entered a
count down for maximum shunt time as defined in the auxiliary
setting begins, if the door is not closed before the maximum shunt
time, the alarm will be triggered.
AUXILIARY MODE 6
In auxiliary mode 6 the AC-Q41H can trigger the auxiliary relay if it
detects that the door has been forced. In this mode the auxiliary
input should be wired to the magnetic contact switch on the door.
The auxiliary relay should be wired to the alarm system. If the door
is forced open the controller will wait for the forced door delay time
and then activate the auxiliary relay. The auxiliary setting defines
the forced door delay.
AC-Q41H
Page 31
07/04
AC-Q41H
Auxiliary Mode Reference Guide
The following are brief descriptions of each of the AC-Q41H's
auxiliary modes. To use these features refer to "Setting the Auxiliary
Mode" on page 28.
AUXILIARY MODE 0
In auxiliary mode 0 the AC-Q41H can function as a two door
controller. The auxiliary relay should be attached to the lock on the
second door. The auxiliary setting defines the door open time for
the second door. The auxiliary input should be attached to the REX
button for the second door.
AUXILIARY MODE 1
In auxiliary mode 1 the AC-Q41H can function as a two door
controller. The auxiliary relay should be attached to the lock on the
second door. The auxiliary setting defines the door open time for
the second door. The auxiliary input can switch the mode of
operation of the controller between Normal and Secure Mode. By
connecting a switch timer to the auxiliary input you can for example
automatically switch the AC-Q41H from Normal Mode during office
hours to Secure mode after office hours.
AUXILIARY MODE 2
In auxiliary mode 2 the auxiliary relay can function as a general
purpose timed switch that can be activated when the star button on
the AC-Q41H is pressed. The auxiliary setting defines how long the
auxiliary relay should be activated. The auxiliary input can switch
the mode of operation of the controller between Normal and Secure
Mode. By connecting a switch timer to the auxiliary input you can
for example automatically switch the AC-Q41H from Normal Mode
during office hours to Secure mode after office hours.
AUXILIARY MODE 3
In auxiliary mode 3 the auxiliary output is activated if the AC-Q41H
is tampered, i.e. the case tamper or back tamper is triggered. The
auxiliary input can switch the mode of operation of the controller