background image

Quick Installation Guide

00825-0100-4662, Rev CB

July 2011

Rosemount 8732

16

Supply Wire Requirements

Use 14 to 18 AWG wire rated for the proper temperature of the application. For connections 
in ambient temperatures above 140 °F (60 °C), use a wire rated for 176 °F (80 °C). For 
ambients greater than 176 °F (80 °C), use a wire rated for 230 °F (110 °C). For DC powered 
transmitters with extended power cable lengths, verify that there is a minimum of 12 V DC at 
the terminals of the transmitter.

Disconnects

Connect the device through an external disconnect or circuit breaker. Clearly label the 
disconnect or circuit breaker and locate it near the transmitter and per local electrical 
control.

Overcurrent Protection

The Rosemount 8732 Flowmeter Transmitter requires overcurrent protection of the supply 
lines. Maximum ratings of overcurrent devices are as follows:

Connect 4–20 mA Loop External Power Source

For transmitters with non-I.S. Output, the 4–20 mA output loop signal may be powered 
internally or externally. The default position of the internal/external analog power jumper is in 
the 

internal

 position. The user-selectable power supply jumper is located on the electronics 

board.

Internal

The 4–20 mA analog power loop may be powered from the transmitter itself. Resistance in 
the loop must be 600 ohms or less. If a HART Field Communicator or control system will be 
used, it must be connected across a minimum of 250 ohms resistance in the loop.

External

HART multidrop installations require a 10–30 V DC external analog power source. If a HART 
Field Communicator or control system is to be used, it must be connected across a 

Figure 13.  Power Supply Current

Table 6.  Overcurrent Ratings

Power System

Fuse Rating

Manufacturer

95-250 V AC

250 V; 2 Amp, Quick Acting

Bussman AGCI or Equivalent

42 V DC

50 V, 3 Amp, Quick Acting

Bussman AGCI or Equivalent

12

18

24

30

36

42

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Power Supply (Volts)

I = 10/V
I = Supply current requirement (Amps)
V = Power supply voltage (Volts)

Supply Current (Amp

s

)

4662RevCBQIG.fm  Page 16  Wednesday, July 6, 2011  3:41 PM

Summary of Contents for 8732E

Page 1: ...B July 2011 Rosemount 8732 Start Step 1 Pre Installation Step 2 Handling Step 3 Mounting Step 4 Installation Flanged Sensors Wafer Sensors Sanitary Sensors Step 5 Grounding Step 6 Wiring Step 7 Basic Configuration End Rosemount 8732E Magnetic Flowmeter System Transmitter and Sensor ...

Page 2: ...t sensor that is located in an explosive atmosphere WARNING The sensor liner is vulnerable to handling damage Never place anything through the sensor for the purpose of lifting or gaining leverage Liner damage can render the sensor useless To avoid possible damage to the sensor liner ends do not use metallic or spiral wound gaskets If frequent removal is anticipated take precautions to protect the...

Page 3: ...equirements Mechanical Considerations The mounting site for the Rosemount 8732 transmitter should provide enough room for secure mounting easy access to conduit ports full opening of the transmitter covers and easy readability of the LOI screen see Figure 1 If the Rosemount 8732 is mounted separately from the sensor it is not subject to limitations that might apply to the sensor Figure 1 Rosemount...

Page 4: ...dware 2 Attach the Rosemount 8732 to the mounting bracket using the mounting screws Identify Options and Configurations The standard application of the 8732 includes a 4 20 mA output and control of the sensor coils and electrodes Other applications may require one or more of the following configurations or options Multidrop Communications Digital Output Digital Input Pulse Output Additional option...

Page 5: ... Housing The electronics housing can be rotated on the sensor in 90 increments by loosening the four mounting bolts on the bottom of the housing and reinstalling the bolts When the housing is returned to its original position be sure the surface is clean and there is no gap between the housing and the sensor STEP 2 HANDLING Handle all parts carefully to prevent damage Whenever possible transport t...

Page 6: ...till be highly repeatable Flow Direction The sensor should be mounted so the FORWARD end of the flow arrow shown on the sensor identification tag points in the direction of flow through the sensor Sensor Orientation The sensor should be installed in a position that ensures the sensor remains full during operation Vertical installation allows upward process fluid flow and keeps the cross sectional ...

Page 7: ...tions to adjacent devices or piping The gasket material selected must be compatible with the process fluid and operating conditions Metallic or spiral wound gaskets can damage the liner Gaskets are required on each side of a grounding ring All other applications including sensors with lining protectors or a grounding electrode require only one gasket on each end connection Flange Bolts NOTE Do not...

Page 8: ...sted torque values or until the leak between the process and sensor flanges stop If leakage has not stopped at the suggested torque values the bolts can be tightened in additional 10 increments until the joint stops leaking or until the measured torque value reaches the maximum torque value of the bolts Practical consideration for the integrity of the liner often leads the user to distinct torque ...

Page 9: ... 165 280 140 250 300 30 inch 750 mm 195 415 165 375 360 36 inch 900 mm 280 575 245 525 Table 2 Flange Bolt Torque and Bolt Load Specifications for 8705 PTFE ETFE liner Size Code PN10 PN 16 PN 25 PN 40 Line Size Newton meter Newton Newton meter Newton Newton meter Newton Newton meter Newton 005 0 5 inch 15 mm 10 4400 010 1 inch 25 mm 20 10100 015 1 5 inch 40 mm 50 16100 020 2 inch 50 mm 60 20100 03...

Page 10: ...e bottom side of the sensor between the pipe flanges Stud specifications are listed in Table 3 NOTE Using carbon steel bolts on smaller line sizes 0 15 through 1 inch 4 through 25 mm rather than the required stainless steel bolts will degrade performance Size Code Line Size Polyurethane Linatex and Neoprene Liners PN 10 PN 16 PN 25 PN 40 Newton meter Newton Newton meter Newton Newton meter Newton ...

Page 11: ... the flange bolts All sensors require a second torquing 24 hours after initial flange bolt tightening Table 3 Stud Specifications Nominal Sensor Size Stud Specifications 0 15 1 inch 4 25 mm 316 SST ASTM A193 Grade B8M Class 1 threaded mounted studs 1 5 8 inch 40 200 mm CS ASTM A193 Grade B7 threaded mounting studs Figure 7 Gasket Placement with Centering Rings Table 4 Rosemount 8711 Torque Specifi...

Page 12: ...ied between the IDF fitting and the process connection fitting such as a Tri Clamp fitting on all Rosemount 8721 Sanitary sensors except when the process connection fittings are not supplied and the only connection type is an IDF fitting Alignment and Bolting Standard plant practices should be followed when installing a magmeter with sanitary fittings Unique torque values and bolting techniques ar...

Page 13: ...e 5 Process Grounding Installation Process Grounding Options Type of Pipe Grounding Straps Grounding Rings Grounding Electrode Lining Protectors Conductive Unlined Pipe See Figure 9 Not Required Not Required See Figure 10 Conductive Lined Pipe Insufficient Grounding See Figure 10 See Figure 9 See Figure 10 Non Conductive Pipe Insufficient Grounding See Figure 11 See Figure 12 See Figure 11 Figure ...

Page 14: ...tallation Guide 00825 0100 4662 Rev CB July 2011 Rosemount 8732 14 Figure 11 Grounding with Grounding Rings or Lining Protectors Figure 12 Grounding with Grounding Electrode Grounding Rings or Lining Protectors ...

Page 15: ...h the conduit connections in your magnetic flowmeter system Run the power cable from the power source to the transmitter Run the coil drive and electrode cables between the sensor and transmitter Prepare the ends of the coil drive and electrode cables as shown in Figure 14 Limit the unshielded wire length to 1 inch on both the electrode and coil drive cables Excessive lead length or failure to con...

Page 16: ...ansmitters with non I S Output the 4 20 mA output loop signal may be powered internally or externally The default position of the internal external analog power jumper is in the internal position The user selectable power supply jumper is located on the electronics board Internal The 4 20 mA analog power loop may be powered from the transmitter itself Resistance in the loop must be 600 ohms or les...

Page 17: ...output and or digital input output consult the comprehensive product manual Transmitter to Sensor Wiring A single dedicated conduit run for the coil drive and electrode cables is needed between a sensor and a remote transmitter Bundled cables in a single conduit are likely to create interference and noise problems in your system Use one set of cables per conduit run Figure 14 Cable Preparation Det...

Page 18: ...Guide 00825 0100 4662 Rev CB July 2011 Rosemount 8732 18 Figure 15 Conduit Preparation Wrong Correct Coil Drive and Electrode Cables Power Outputs Power Outputs Coil Drive and Electrode Cables Power Outputs Power Outputs ...

Page 19: ...Wiring Connections Using Individual Coil and Signal Cable Sensor to Remote Mount Transmitter Connections Table 7 Cable Requirements Description Length Part Number Signal Cable 20 AWG Belden 8762 Alpha 2411 equivalent ft m 08712 0061 0001 08712 0061 0003 Coil Drive Cable 14 AWG Belden 8720 Alpha 2442 equivalent ft m 08712 0060 0001 08712 0060 0013 Combination Signal and Coil Drive Cable 18 AWG 1 1 ...

Page 20: ...jam screw an additional 1 2 turn counterclockwise to secure the cover Note Application of excessive torque may strip the threads 5 Verify that the cover cannot be removed Step 7 Basic Configuration Once the magnetic flowmeter is installed and power has been supplied the transmitter must be configured through the basic setup These parameters can be configured through either a local operator interfa...

Page 21: ...Upper Range Value The upper range value URV sets the 20 mA point for the analog output This value is typically set to full scale flow The units that appear will be the same as those selected under the units parameter The URV may be set between 42 ft s to 42 ft s 12 m s to 12 m s There must be at least 1 ft s 0 3 m s span between the URV and LRV LRV Lower Range Value The lower range value LRV sets ...

Page 22: ...ner of the display To deactivate the display lock DL hold the UP arrow for 10 seconds Once deactivated the DL will no longer appear in the lower left hand corner of the display Function HART Fast Keys Process Variables 1 1 Primary Variable PV 1 1 1 PV Percent of Range 1 1 2 PV Analog Output AO 1 1 3 Totalizer Set Up 1 1 4 Totalizer Units 1 1 4 1 Gross Total 1 1 4 2 Net Total 1 1 4 3 Reverse Total ...

Page 23: ...NR Signal Power 8714i R esults D A T rim Digital T rim A uto Zero Universal T rim 4 20 mA V erify V iew R esults T ag Flow Units L ine Size PV UR V PV L R V Cal Number PV Damping Coil Frequency Proc Density PV L SL PV USL PV Min Span A nalog Pulse DI DO Config T otalizer R everse Flow HA R T PV UR V PV L R V A larm T ype T est Pulse Scaling Pulse Width Pulse Mode T est DI 1 DO 2 T otalize Units T ...

Page 24: ...s in the device must be carried out using the appropriate EEx e or EEx n metal cable gland and metal blanking plug or any appropriate ATEX approved cable gland and blanking plug with IP66 rating certified by an EU approved certification body CE Marking Complies with EN 61326 1 2006 For Rosemount 8732E transmitters Complies with Essential Health and Safety Requirements EN 60079 0 2006 EN 60079 1 20...

Page 25: ... Division 1 Groups E F and G T4 at 60 C Hazardous locations Enclosure Type 4X Requires sensors with N5 Approval E5 Explosion proof for Class I Division 1 Groups C and D T6 at 60 C and Dust ignition proof Class II III Division 1 Groups E F and G T5 at 60 C Non incendive for Class I Division 2 Groups A B C and D flammable fluids T4 at 60 C 50 C Ta 60 C Hazardous locations Enclosure Type 4X Canadian ...

Page 26: ...4 Ta 50 C to 60 C Vmax 42 V DC 0575 SPECIAL CONDITIONS FOR SAFE USE X The apparatus is not capable of withstanding the 500V insulation test required by Clause 6 8 1 of EN 60079 15 2005 This must be taken into account when installing the apparatus International Certifications IECEx E7 IECEx Flameproof Certificate No KEM 07 0038X Ex de IIC or Ex de ia IIC T6 50 C Ta 60 C with LOI 20 C Ta 60 C Vmax 2...

Page 27: ...the apparatus NEPSI China E3 NEPSI Flameproof Certificate No GYJ071438X Ex de IIC or Ex de ia IIC T6 50 C Ta 60 C with LOI 20 C Ta 60 C Vmax 250 V AC or 42 V DC EP NEPSI Flameproof Certificate No GYJ071438X Ex de IIB or Ex de ia IIB T6 50 C Ta 60 C with LOI 20 C Ta 60 C Vmax 250 V AC or 42 V DC InMetro Brazil E2 InMetro Flameproof Certificate No NCC 5030 08 BR Ex de IIC or BR Ex de ia IIC T6 50 C ...

Page 28: ...ations are available on the Rosemount 570TM Approval Codes Rosemount 8705 Sensor Rosemount 8707 Sensor Rosemount 8711 Sensor Rosemount 8721 Sensors For Non fla mmable Fluids For Flamma ble Fluids For Non fla mmable Fluids For Flamma ble Fluids For Non fla mmable Fluids For Flamma ble Fluids For Non flammable Fluids NA N0 ND N1 N5 N7 ND NF E1 E2 E3 E5 2 2 Available in line sizes up to 8 in 200 mm o...

Page 29: ...logy Drive and 8200 Market Boulevard Eden Prairie MN 55344 3695 Chanhassen MN 55317 9687 USA USA to which this declaration relates is in conformity with the provisions of the European Community Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of harmonized or applicable technical standards and when applicable or requi...

Page 30: ...el 8732E Magnetic Flowmeter Transmitter KEMA 07ATEX0073 X Flameproof with Increased Safety Terminal s Intrinsically Safe Output s Dust Equipment Group II Category 2 G Ex d IIB IIC T6 Ex de IIB IIC T6 Ex e IIB IIC Junctionbox Equipment Group II Category 2 1 G Ex de ia IIB IIC T6 Transmitter Equipment Group II Category 1 G Ex ia IIC Equipment Group II Category 1 D Ex tD A20 IP66 T100 ºC EN 60079 0 2...

Page 31: ...I Category 3 1 G Ex nA nL ia IIC T4 EN 60079 0 2006 EN 60079 15 2005 EN 60079 11 2007 ATEX Notified Bodies for EC Type Examination Certificate KEMA Notified Body Number 0344 Utrechtseweg 310 6812 AR Arnhem P O Box 5185 6802 ED Arnhem The Netherlands Postbank 6794687 Baseefa Notified Body Number 1180 Rockhead Business Park Staden Lane Buxton Derbyshire SK17 9RZ United Kingdom ATEX Notified Body for...

Page 32: ...Quick Installation Guide 00825 0100 4662 Rev CB July 2011 Rosemount 8732 32 ...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ......

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ......

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ......

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ......

Page 53: ......

Page 54: ......

Page 55: ......

Page 56: ......

Page 57: ......

Page 58: ......

Page 59: ......

Page 60: ......

Reviews: