Quick Installation Guide
00825-0100-4809, Rev DB
December 2009
Flanged 485 Annubar
5
S
TEP
1
CONTINUED
...
NOTE
• Consult the factory for instructions regarding use in square or rectangular ducts.
• “In Plane A” means the sensor is in the same plane as the elbow. “Out of Plane A”
means the sensor is perpendicular to the plane of the elbow.
• If proper lengths of straight run are not available, position the mounting such that 80%
of the run is upstream and 20% is downstream.
• Use straightening vanes to reduce the required straight run length.
• Row 6 in Table 1 applies to gate, globe, plug, and other throttling valves that are
partially opened, as well as control valves.
Misalignment
485 Annubar installation allows for a maximum misalignment of 3°.
Figure 1. Misalignment
Upstream Dimensions
Downst
re
am
Dim
e
nsions
Without
Straightening
Vanes
With Straightening
Vanes
In
Plane A
Out of
Plane A
A’
C
C’
B
5
18
—
18
—
—
8
—
4
—
4
4
4
6
30
—
30
—
—
8
—
4
—
4
4
4
±3°
±3°
±3°