Quick Installation Guide
00825-0100-4809, Rev DB
December 2009
Flanged 485 Annubar
11
S
TEP
5: I
NSERT
THE
A
NNUBAR
1. Align the flow arrow on the head with the direction of flow. Assemble the bar to the
mounting flange using a gasket, bolts, and nuts.
2. Tighten the nuts in a cross pattern to allow even compression of the gasket.
3. If opposite side support is threaded, apply an appropriate thread sealing compound to
the support plug threads and tighten until no leakage occurs.
4. If opposite side support is a socket weld fitting, insert the plug into the sockolet fitting
until the parts contact. Retract the plug
1
/
16
-in. (1,6 mm) remove the Annubar sensor and
apply fillet weld per local codes.
S
TEP
6: M
OUNT
THE
T
RANSMITTER
Transmitter Mounting, Direct Mount Head with Valves
It is not necessary to retract the Annubar when direct mounting a transmitter with valves.
1. Place PTFE O-rings into grooves on the Annubar head.
2. Align the high side of the transmitter to the high side of the sensor (“Hi” is stamped on the
side of the head) and install.
3. Tighten the nuts in a cross pattern to 400 in•lb (45 N•m).
Transmitter Mounting with Remote Mount Head
Temperatures in excess of 250 °F (121 °C) at the sensor module diaphragms will damage
the transmitter. Remote mounted transmitters are connected to the sensor by means of
impulse piping, which allows process temperatures to decrease to a point where the
transmitter is no longer vulnerable.
Different impulse piping arrangements are used depending on the process fluid and must be
rated for continuous operation at the pipeline design pressure and temperature. A minimum
of
1
/
2
-in. (12 mm) outer diameter stainless steel tubing with a wall thickness of at least
0.035-in. (0,9 mm) is recommended including and under 600# ANSI (DN50 PN100). Above
600# ANSI (DN50 PN100), stainless steel tubing with
1
/
16
-in. wall thickness.Threaded pipe
fittings are not recommended because they create voids where air can become entrapped
and create leakage points.