Reference Manual
00809-0100-4021, Rev FB
August 2011
4-17
Rosemount 3144P
F
OUN
DATION
F
ie
ldb
us
a. Go to MODE_BLK.TARGET
b. Choose OOS (0x80)
2.
Go to CHANNEL
a. Choose Sensor 1
3.
Go to L_TYPE
a. Choose Direct
4.
Go to XD_Scale
a. Choose UNITS_INDEX to be °F
b. Set 0% = –200, set 100% = 500
5.
Go to OUT_SCALE
a. Choose UNITS_INDEX to be °F
b. Set the 0 and 100 scale to be the same as in Step 4b
6.
Put the AI Block back into Auto mode
7.
Follow Host Procedure to download schedule into Block