![Rosemount 3144P User Manual Download Page 101](http://html1.mh-extra.com/html/rosemount/3144p/3144p_user-manual_1487451101.webp)
Reference Manual
00809-0100-4021, Rev FB
August 2011
4-33
Rosemount 3144P
F
OUN
DATION
F
ie
ldb
us
LCD Display
NOTE
For Rosemount 3144P transmitters with F
OUNDATION
fieldbus, the following
LCD display options are not used: Bar graph, Sensor 1, Sensor 2, Differential,
Multidrop, and Burst Mode.”
The following are the default tags for each of the possible Function blocks
which display data on the LCD
Table 4-14. LCD Display Error Warning Descriptions
Message
LCD top line
LCD bottom line
RB.DETAILED_STATUS
Sensor Transducer Block Error
“Error”
“DVICE”
Manufacturing Block Integrity Error
“Error”
“DVICE”
Hardware/Software Incompatible
“Error”
“DVICE”
Non-volatile Memory Integrity Error
“Error”
“DVICE”
ROM Integrity Error
“Error”
“DVICE”
Lost Deferred NV Data
“Error”
“DVICE”
NV Writes Deferred
No Errors Displayed
ADB Transducer Block Error
No Errors Displayed
STB.SENSR_DETAILED_STATUS
Invalid Configuration
“Error”
“SNSOR”
ASIC RCV Error
“Error”
“SNSOR”
ASIC TX Error
“Error”
“SNSOR”
ASIC Interrupt Error
“Error”
“SNSOR”
Reference Error
“Error”
“SNSOR”
ASIC Configuration Error
“Error”
“SNSOR”
Sensor 1 Open
“Error”
“SNSOR”
Sensor 1 Shorted
“Error”
“SNSOR”
Terminal (Body) Temperature Failure
“Error”
“SNSOR”
Sensor 1 Out of Operating Range
No Errors Displayed
Sensor 1 Beyond Operating Limits
“Error”
“SNSOR”
Terminal (Body) Temperature Out of Operating Range
No Errors Displayed
Terminal (Body) Temperature Beyond Operating Limits
“Error”
“SNSOR”
Sensor 1 Degraded
“Error”
“SNSOR”
Calibration Error
“Error”
“SNSOR”
Sensor 2 Open
“Error”
“SNSOR”
Sensor 2 Shorted
“Error”
“SNSOR”
Sensor 2 Out of Operating Range
No Errors Displayed
Sensor 2 Beyond Operating Limits
“Error”
“SNSOR”
Sensor 2 Degraded
“Error”
“SNSOR”
Sensor Drift Alert
“Error”
“SNSOR”
Hot Backup Active
“Error”
“SNSOR”
Thermocouple Degradation Alert
“Error”
“SNSOR”
Block Name
LCD bottom line
Transducer
“TRANS”
AI 1400
“AI 14”
AI 1500
“AI 15”
AI 1600
“AI 16”
PID 1700
“PID 1”
PID 1800
“PID 1”
ISEL 1900
“ISEL”
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182