Reference Manual
00809-0100-4021, Rev FB
August 2011
Rosemount 3144P
4-16
F
OUNDA
TION
Fieldbus
NOTE
To avoid configuration errors, only select Engineering Units for XD_SCALE
and OUT_SCALE that are supported by the device. The supported units
are:
When the engineering units of the XD_SCALE are selected, this changes
the engineering units of the PRIMARY_VALUE_RANGE in the Transducer
Block to the same units.
THIS IS THE ONLY WAY TO CHANGE THE ENGINEERING UNITS IN
THE SENSOR TRANSDUCER BLOCK, PRIMARY_VALUE_RANGE
parameter.
Configuration Examples
Sensor Type: 4-wire, Pt 100
= 385.
Desired measurement process temperature in the –200 to 500 °F range.
Monitor the transmitter electronics temperature in the –40 to 185 °F range.
Transducer Block
If Host System Supports Methods:
1.
Click on Methods
2.
Choose Sensor Connections
(1)
3.
Follow on-screen instruction to setup Sensor 1 as a 4-wire, Pt 100
= 385
If Host System Does Not Support Methods:
1.
Put transducer block into OOS mode.
a. Go to MODE_BLK.TARGET
b. Choose OOS (0x80)
2.
Go to SENSOR_CONNECTION
a. Choose 4-wire (0x4)
3.
Go to SENSOR_TYPE
a. Choose PT100A385
4.
Put the transducer block back into Auto mode.
AI Blocks (Basic Configuration)
AI1 as Process Temperature
1.
Put the AI Block into OOS mode
Temperature (Channel 1 and 2)
Terminal (Body) Temperature
°
C
°
C
°
F
°
F
K
K
°R
R
mV
(1)
Some choices may not be available due to the current configuration of the device.
Examples:
1) Sensor 2 cannot be configured at all if Sensor 1 is set up as a 4-wire sensor
2) If Sensor 2 is configured, Sensor 1 can not be set up as a 4-wire sensor (and vise-versa)
3) When selecting a thermocouple as the sensor type, a 3- or 4-wire connection cannot be
selected.
In this situation, configure the other sensor as “Not used.” This will clear the dependencies
that are preventing the configuration of the desired sensor.