Quick Installation Guide
00825-0100-4716, Rev DA
October 2009
Rosemount 3095 MultiVariable
7
S
TEP
2
CONTINUED
...
• Installing a Shielded 3095 RTD Cable (See Figure 4)
Note: Shielded cable is intended for use in a conduit.
a.Fully engage the black cable connector to the 3095 RTD Connector.
b.Tighten the cable adapter until metal contacts metal.
Figure 4. Shielded RTD Cable
• Installing a ATEX/IECEx Flameproof 3095 RTD Cable (See Figure 5)
a.Fully engage the black cable connector to the 3095 RTD Connector.
b.Tighten the cable adapter and cable gland until metal contacts metal.
Figure 5. ATEX/IECEx Flameproof RTD Cable
7. Check all process connections for leaks.
8. Connect the appropriate wiring (see Step 5). Ground the transmitter according to
national and local electrical codes. Install field wiring grounding (optional).
Cable Adapter
1
/2–14 NPT
Black Cable Connector
Black Cable Connector/ RTD Connector
Cable Adapter
Cable Gland
RTD Cable Gland CM20