Quick Installation Guide
00825-0100-4716, Rev DA
October 2009
Rosemount 3095 MultiVariable
20
G
ATEX Type n
Certificate Number: BAS98ATEX3360X
II 3 G
Ex nL IIC T5 (T
amb
= –45 °C to 40 °C)
Ex nL IIC T4 (T
amb
= –45 °C to 70 °C)
U
i
= 55V
The apparatus is designed for connection to a remote temperature sensor such as a
resistance temperature detection (RTD)
Special Conditions for Safe Use
The 3095, when fitted with the transient terminal block (order code B), are not capable
of withstanding the 500 volts insulation test required by EN60079-15 Clause 6.8.1. This
condition must be accounted for during installation.
H
ATEX Flameproof
Certificate Number: KEMA02ATEX2320X
II 1/2 G
Ex d IIC T5 (-50°C
T
amb
80°C)
T6 (-50°C
T
amb
65°C)
1180
Special Conditions for Safe Use (x):
The device contains a thin wall diaphragm. Installation, maintenance, and use shall take
into account the environmental conditions to which the diaphragm will be subjected. The
manufacturer’s instructions for installation and maintenance shall be followed in detail to
assure safety during its expected lifetime.
P
ATEX Dust
Certificate Number: KEMA02ATEX2321
II 1 D
Ex tD A20 T 90°C(-40°C
T
amb
80°C)
V = 55 Vdc MAX
I = 23 mA MAX
IP66
1180
IECEx Certifications (HART)
4
IECEx Intrinsic Safety
Certificate Number: IECEx BAS06.0070X
Ex ia IIC T4 (-45°C
T
a
70°C)
Ex ia IIC T5 (-45°C
T
a
40°C)
Table 6. Input Parameters
HART I.S.
U
i
= 30Vdc
I
i
= 200 mAdc
P
i
= 1.0 W
C
i
= 12 nF
L
i
= 0
Summary of Contents for 3095MF Series
Page 29: ...Quick Installation Guide 00825 0100 4716 Rev DA October 2009 Rosemount 3095 MultiVariable 29 ...
Page 30: ...Quick Installation Guide 00825 0100 4716 Rev DA October 2009 Rosemount 3095 MultiVariable 30 ...
Page 31: ...Quick Installation Guide 00825 0100 4716 Rev DA October 2009 Rosemount 3095 MultiVariable 31 ...
Page 32: ...Quick Installation Guide 00825 0100 4716 Rev DA October 2009 Rosemount 3095 MultiVariable 32 ...