RONK Automatic Transfer Switch Owner’s Manual
21
MANUAL TRANSFER
MANUAL TRANSFER OF MECHANISM
Manual transferring is not recommended. If the transfer switch
fails to transfer in an emergency, an optional manual transfer
may be performed. Caution must be taken to confirm that
the transfer switch is isolated from all possible load sources
before transferring. Always remove the handle from the manual
transfer handle lever location after each transfer.
100A/200A MANUAL TRANSFER
In 100 and 200A transfer switches, the manual transfer lever
located on the contactor is used to manually transfer between
the utility and generator position. With the lever facing up
toward the normal side, the switch will be in the normal position.
With the lever down facing toward the emergency side, the
switch will be in the emergency position.
400A MANUAL TRANSFER
In 400A transfer switches, the manual transfer lever located on
the contactor is used to manually transfer between the utility
and generator position. A separate removable lever handle is
used to transfer the mechanism. The transfer switch is in the
utility position when reference A on the contactor is set to the
ON position and reference B is set to the OFF position. The
transfer switch is in the generator position when reference A on
the contactor is set to the OFF position and reference B is set to
the ON position. The mechanism is transferred by moving the
lever handle in the down position. See transfer instructions on
the switch mechanism. Never transfer under a load condition.
Always remove the handle from the manual transfer lever
location after each transfer.
!
WARNING
Never perform a manual transfer while the
transfer switch is under load. Manual transfer is
not recommended. If performing an emergency
manual transfer, be certain to isolate the transfer
switch from all power and load sources.
!
WARNING
Never allow the removable lever handle to come
in contact with live wires or terminals.
!
WARNING
Never allow the removable lever handle to come
in contact with live wires or terminals.
Figure 10 - Removable Lever Handle
Figure 11 - Manual Transfer Lever Locations
Manual
Transfer
Lever
Utility
On=Connected
Off=Disconnected
Generator
On=Connected
Off=Disconnected
Summary of Contents for 100-600 AMP
Page 1: ...OWNER S INSTALLATION MANUAL 100 600 AMP RONK Automatic Transfer Switch...
Page 30: ...30 RONK Automatic Transfer Switch Owner s Manual NOTES...
Page 31: ...RONK Automatic Transfer Switch Owner s Manual 31...