RS-500 WIC, RS-500M, and RS-600M Door Training Guide 

RS-500/RS-600 Door and RS-500M/RS-600M Door – EOF1/EOF2: 

 

Place the door in Jog Mode. 

o

 

If the door does not jog: 

 

Open the controller and check the status lights on the drive. 

 

If any lights are off or red, the drive is defective. 

 

If the lights are green and amber, proceed to the next step. 

 

Release the brake on the motor. 

 

Return to the controller and determine whether the door will jog. 

 

If the door jogs, the door assembly brake relay is defective. 

 

If the door does not jog, contact RollSeal (1-888-765-5732) while remaining at the door. 

o

 

If the door jogs: 

 

Check the connections on the black and gray cable (CPCs at head unit). 

 

If the issue is not resolved, proceed to the next step. 

 

Open the encoder enclosure and check the wiring to the encoder (orange housing plugged into 

the encoder circuit board). 

 

If the door still does not jog, replace the encoder. 

Walk-In Cooler Door – EOF1/EOF2:

 Follow the codes indicated in Section 8 of this document. 

Section 8: Smart Switch Indicator Lights 

 

 

 

Summary of Contents for RS-500 WIC

Page 1: ...aining Guide NOTICE If you encounter any issues that cannot be resolved using the information in this document contact RollSeal at 1 888 765 5732 Section 1 Comparison of RS 500 Walk In Cooler WIC Door...

Page 2: ...4802 7536C 2 15 November 2021 RS 500 WIC RS 500M and RS 600M Door Training Guide Section 3 Door Wiring Diagrams 3 1 RS 500 WIC Door...

Page 3: ...4802 7536C 3 15 November 2021 RS 500 WIC RS 500M and RS 600M Door Training Guide 3 2 RS 500M RS 600M Door...

Page 4: ...r 5 seconds to disengage Jog Mode The controller will return to normal operating mode and the display will show the Actual Position The controller will not know the door s exact position so it will di...

Page 5: ...5 If P24 0 P26 CMS Off Time 10 If P24 0 PS1 Setup Door Limits PS2 Set Open Limit PS3 Set Close Limit Section 6 Setting Limits PS1 Change Program Limits This can be set to Yes or No To change the Open...

Page 6: ...Closing Over Speed Fault FE RS 500M RS 600M Door Code Condition Panel Movement Problem Area Recommended Action s EO1 Opening Home Switch Tripped Home Switch Check wiring Ensure Home switch arm is ful...

Page 7: ...d determine whether the door will jog If the door jogs the door assembly brake relay is defective If the door does not jog contact RollSeal 1 888 765 5732 while remaining at the door o If the door jog...

Page 8: ...00 WIC doors and RS 500M RS 600M doors RS 500 WIC doors use a FLY sensor as an auxiliary safety RS 500M RS 600M doors use an egress strap as an auxiliary safety 1 If the switch lights up but does not...

Page 9: ...ondition Possible Cause s Solid Green Slowly Flashing Green Operation is normal N A Quickly Flashing Green Current is over load Drive is operating between 120 and 200 of rated load Slowly Flashing Red...

Page 10: ...turn fan is not operational Supply Fan L ON Green The supply fan is running at the designated RPM Supply Fan L FAIL Red The supply fan is not operational Heat ON Green At least one of the two fans is...