4802-7536C 

10 

15 November 2021 

RS-500 WIC, RS-500M, and RS-600M Door Training Guide 

The LEDs at the top-left corner of the PCB 204 provide greater detail about the status of the Condensation Management 

System. 

LED 

Color 

Cause 

Power 

Green 

Input power is being supplied to the PCB 204. 

CMS Status: ON 

Green 

The PCB 204 recognizes that the CMS is operational. 

CMS Status: Fail 

Red 

The PCB 204 has detected an issue with at least one of the CMS’s components. 

Return Fan (R): ON 

Green 

The return fan is running at the designated RPM. 

Return Fan (R): Fail 

Red 

The return fan is not operational. 

Supply Fan (L): ON 

Green 

The supply fan is running at the designated RPM. 

Supply Fan (L): FAIL 

Red 

The supply fan is not operational. 

Heat: ON 

Green 

At least one of the two fans is operational. The heating element should be engaged. 

Heat: ++ 

Green 

The CMS is in “boost” configuration and is reacting to a requirement for slightly more heat. The LED will turn 

off when the requirement is met. 

Heat: Low Diff 

Red 

The temperature sensors do not read the expected temperature difference. 

Heat: Hi Temp 

Red 

The supply-side temperature sensor has reached the factory-set maximum temperature. 

Heat: Amb Diff 

Red 

This LED is currently unused. It is reserved for future use. 

Over Pressure 

Red 

This LED is currently unused. It is reserved for future use. 

 

 

Summary of Contents for RS-500 WIC

Page 1: ...aining Guide NOTICE If you encounter any issues that cannot be resolved using the information in this document contact RollSeal at 1 888 765 5732 Section 1 Comparison of RS 500 Walk In Cooler WIC Door...

Page 2: ...4802 7536C 2 15 November 2021 RS 500 WIC RS 500M and RS 600M Door Training Guide Section 3 Door Wiring Diagrams 3 1 RS 500 WIC Door...

Page 3: ...4802 7536C 3 15 November 2021 RS 500 WIC RS 500M and RS 600M Door Training Guide 3 2 RS 500M RS 600M Door...

Page 4: ...r 5 seconds to disengage Jog Mode The controller will return to normal operating mode and the display will show the Actual Position The controller will not know the door s exact position so it will di...

Page 5: ...5 If P24 0 P26 CMS Off Time 10 If P24 0 PS1 Setup Door Limits PS2 Set Open Limit PS3 Set Close Limit Section 6 Setting Limits PS1 Change Program Limits This can be set to Yes or No To change the Open...

Page 6: ...Closing Over Speed Fault FE RS 500M RS 600M Door Code Condition Panel Movement Problem Area Recommended Action s EO1 Opening Home Switch Tripped Home Switch Check wiring Ensure Home switch arm is ful...

Page 7: ...d determine whether the door will jog If the door jogs the door assembly brake relay is defective If the door does not jog contact RollSeal 1 888 765 5732 while remaining at the door o If the door jog...

Page 8: ...00 WIC doors and RS 500M RS 600M doors RS 500 WIC doors use a FLY sensor as an auxiliary safety RS 500M RS 600M doors use an egress strap as an auxiliary safety 1 If the switch lights up but does not...

Page 9: ...ondition Possible Cause s Solid Green Slowly Flashing Green Operation is normal N A Quickly Flashing Green Current is over load Drive is operating between 120 and 200 of rated load Slowly Flashing Red...

Page 10: ...turn fan is not operational Supply Fan L ON Green The supply fan is running at the designated RPM Supply Fan L FAIL Red The supply fan is not operational Heat ON Green At least one of the two fans is...

Reviews: