background image

    seconds  under  the  “timer  settings”  menu.  Press 

the “1/0” key or toggle the parts sensor to restart 

the control.  The auxiliary output can be set up to 

turn on a signaling device.  See the section that 

describes the auxiliary output for more details. 

 

19.  Auxiliary Output Settings

 

The “Aux Output Mode” menu contains the menu that 

controls the auxiliary output (Aux Out) operation.  

A.  The  factory-default  “Normal”  setting  allows  the 

auxiliary output to turn on and off with the output 

of the feeder.   

B. The auxiliary output can be set to have its signal 

inverted  from  the  output  of  the  feeder.    Set  the 

“Aux Out” parameter to “Invert” to activate it.   

C. The auxiliary output can be set so that the alarm 

signal can indicate when the “Empty Bowl” timer 

has  timed  out.  Set  the  “Aux  Out”  parameter  to 

“Alarm” to activate it. 

D. The auxiliary output can be set so that the alarm 

signal  can  be  inverted  when  the  “Empty  Bowl” 

timer has timed out. Set the “Aux Out” parameter 

to “Inv Al” to activate it. 

E.  The  auxiliary  output  can  be  set  so  that  an  air 

solenoid can be activated 1 second before feeding 

begins and continue for 4 seconds after feeding 

ends.  This feature is helpful for parts orientation.  

Set the “Aux Out” parameter to “Air Jet” to activate 

this feature. 

20.  Diagnostics

 

A.  The  first  menu  item  under  the  diagnostic  menu 

shows the software revision level.   

B.  The  next  four  items  under  the  software  revision 

level show certain software registers that may be 
helpful  to  Rodix  staff  while  troubleshooting  over 
the phone. 

21.  Security Settings

 

The “Security” menu contains the portion of the menu 

that controls access to the program menu settings.  

When enabled, the security code is a number from 

000  to  999.    The  preset  code  is  123.    It  may  be 

changed. 

A.  The  control  comes  with  the  security  setting 

“Unlocked”  so  the  control  can  be  set  up.    The 

amplitude  can  be  adjusted  from  the  normal 

operating display.  Press and hold “Enter” to enter 

the  program  menu  and  adjust  the  software 

settings. 

B.  The  amplitude  only  (Ampl.  Only)  adjustment 

allows operators to adjust the amplitude through 

the  normal  operating  display,  but  not  get  to  the 

program menu settings without the security code.   

C.  The  “Lock”  setting  locks  the  control  from  any 

adjustment without the use of the security code.   
If the security code has been forgotten, enter the 
security code #010, 

press and hold

 “Enter” until 

entry has been granted.  Note: ignore the “Wrong 
Security  Code”  message.    Once  in  the 
programming  menu  be  sure  to  set  the  security 
code. 

22.  Default Memory

 

Occasionally it is nice to get back to a known setting. 
Once  a  feed system has  been set  up  properly,  the 
setting  should  be  manually  saved  into  the  “Save 
Settings1”  memory.    If  an  operator  disturbs  the 
settings, the “Restore Settings1” feature can restore 
the control to a known good set up.  When different 
parts are used on the same feed system, two other 
memory locations called “Save Setting2” and “Save 
Settings3” can be used for other parts. Operators can 
recall settings 1, 2 or 3 based on the part being used.  
The  “Factory  Reset”  selection  will  put  the  original 
factory settings into the memory. 

23.  Language

 

The run display and programming menus can be set 
to  display  in  English,  Spanish  (Espa

ñ

ol),  French 

(Français), or German (Deutsch).  

 

24.  Over Current Protection

 

The control has a coarse over-current fault protection 
that trips when the output is above the rated current 
shown  in  the  chart  below.    Under  certain  load 
conditions  the  VF-12  &  VF-18  controls  will  supply 
less current when operating below 16 Hz.   

 

Rating with 

120V input

Rating with 

240V input

120V Rating 

below 16Hz

VF3

3 Amps

1.5 Amps

N/A 

VF9

9 Amps

4.5 Amps

N/A 

VF12

12 Amps

6 Amps

8 Amps

VF18

18 Amps

9 Amps

14 Amps

The  operator  should  monitor  the  output  current  to 
ensure that it is within the desired range.  If an “Over 
Current”  occurs,  press  the  “1/0”  key  to  restart  the 
control.    The  operator  should  also  monitor  the 
temperature of the coils on the vibratory feeder.  The 
coils should never be too hot to hold by hand.   

 

25. CFR Set Point 

The CFR set point sets the amplitude vibration level 
that the control regulates to. The VF Series control 
adjusts  the  amplitude  automatically  to  match  the 

CFR set point. The CFR set point can be adjusted by 
the depression of the “UP” and “DOWN” arrows keys. 
Holding an arrow key down will adjust the amplitude 
setting instead of the CFR set point.  The CFR set 
point can also be controlled by a 4-20mA signal. 

 

 

The CFR set point only appears on the display when 
the “Amplitude Source” menu under power settings 
is set to “Auto Track” and the CFR sensor is attached.   

 

26. Fault Messages 

The VF control has error and warning messages 
that relate to “Over-Amps”, “Over-Temp” and Bowl 
out of parts timers.  To clear the message or fault, 
press the “1/0” button twice. “Coarse and Fine Scan 
Error” mean not enough vibration was measured 
during an Autoscan. Reduce Resonate Threshold. 

 

 

WARNING: 

Fuses should be replaced with Littelfuse 3AB 

"Fast Acting" type or equivalent of 

manufacturer's original value. 

Mounting this control on a vibrating surface will 
void the warranty. 

 

 

Warranty 

Rodix Control Products are Warranted to be free from 
defects in material and workmanship under normal use 
for a period of two years from date of shipment.  

For 

the  full  description  of  the  warranty,  terms,  and  software 
license, please contact the factory. 

 

For  assistance  installing  or  operating  your  Rodix  Feeder 
Cube®  please  call  the  factory  or  visit  our  web  site. 
Technical help is available to answer your questions and 
email any needed information.  To return a control for IN or 
OUT of warranty service, please ship it prepaid to: 

Rodix Inc.,  ATTN: Repair Department 

If under warranty, Rodix will repair or replace your control 
at no charge; If out of warranty, we will repair it and you will 
be billed for the repair charges (Time and Material) plus the 
return  freight.    Quotes  for  repairs  are  available  upon 
request.  A brief note describing the symptoms helps our 
technicians address the issue. 

 

Feeder Cube® and Auto Tune® are registered TM of Rodix Inc. 
Banner

 is a registered Trademark of Banner Engineering Corp, 

9714 10th Ave, Minneapolis, MN 55441 

 

RODIX, INC.

 

2316 23

rd

 Avenue, Rockford, IL 61104 

Toll Free (800) 562-1868

 

E-mail  [email protected] 

www.rodix.com 

1 VF Set Up Ver1_28D.docx 2/28/2019  Page 6 

Summary of Contents for Autotune Series

Page 1: ...Rated Output Current 3 Amps at 120V or 1 5 Amps at 240V Rated for IP54 environment UL rated for Type 5 environment Model Information The Autotune Series of Variable Frequency Feeder Cubes generates an...

Page 2: ...Bl 14 Out LCD Contrast Br Bl 14 Out Danger Shock Hazard E ACCEPTS BOTH OPTIC AND PROX SENSORS NPN OR PNP Analog Gnd 11 7 MASTER CONTROL SM312FP1H OPTICS INPUT 3 Bl OPTIC SENSOR 1 RUN 2 R27 High Voltag...

Page 3: ...nnecting TB1 L2 to the L2 fuse holder Remove the terminal end of the wire connecting the L2 fuse to the power switch and connect it to TB1 L2 1 Parts Sensor Input Photo sensor or Proximity Switch Conn...

Page 4: ...or below the minimum power setting level The amplitude power setting is displayed in the following manner A 50 0 8 Limiting The Maximum Output Of Control The Max Amplitude setting can be adjusted to...

Page 5: ...g is enabled the normal display menu will show a bold F When is shown in bold the control is locked onto the resonate frequency of the feeder C The frequency can be adjusted with an analog 0 10 volt i...

Page 6: ...n will put the original factory settings into the memory 23 Language The run display and programming menus can be set to display in English Spanish Espa ol French Fran ais or German Deutsch 24 Over Cu...

Page 7: ...nate control Steps to Interlock an FC 40 Plus Series to a VF Series Control 1 Add a wire from terminal 2 of the VF master control to TB2 11 of the subordinate control 2 Add a wire from terminal 3 of t...

Page 8: ...r Resets Control to Factory Default Settings Shown in bold Language Pick Language English Espa ol Spanish Fran ais French Deutsch German Normal Display Message Priority The normal operating display sh...

Page 9: ...ensor at least 20 minutes to cure before operation Note It takes 72 hours for the adhesive to fully cure at 70 F Alternatively 8 or M4 screws can be used to mount the sensor to the feeder The mounting...

Page 10: ...f a nearby noise source Solutions for Electrical Noise 1 Use shielded wires for all I O Input Output signals The I O signals may include 4 20mA input Run input Sensor input 0 5VDC input Interlock inpu...