![Rockwell Automation Samsung NX-SCU User Manual Download Page 24](http://html.mh-extra.com/html/rockwell-automation/samsung-nx-scu/samsung-nx-scu_user-manual_1475457024.webp)
24
Using READ in WinGPC
(Receiving from external RS232C (RS485) device)
When SCU is installed in the first slot of PLC system and external
RS232C (RS485) is connected to CH1.
Using WRITE in WinGPC
(Transmitting to external RS232C (RS485) device)
When SCU is installed in the first slot of PLC system and external
RS232C (RS485) is connected to CH1.
READ
(Data READ from
high function unit.)
Condition for READ
Condition for READ
completion
READ
READ completion signal
(Output to the SCU unit)
R0.1: For CH1 receiving
R0.1 turns on when normal data is input
to the RS232C (RS485) device
connected to CH1.
R1.1: For CH1 receiving
When reading received data from
shared memory, turn on R1.1.
Turn on R1.1 when R0.1 is turned off.
R0.1
R1.1
R0.1
R1.1
R100
R101
R100
R1.1
R1.1
R100
R101
WRITE
(Data WRITE to
high-function unit )
Condition for
WRITE
Condition for
WRITE
completion
WRITE
WRITE completion
signal
(Write to the SCU unit)
R0.0: For CH1 sending
When the SCU received correct data,
R0.0 turns on.
R1.0: For CH1 sending
When writing sending data to shared
memory,
turn on R1.0.
Turn off R1.0 when R0.0 is turned on.
R0.0
R1.0
R0.0
R1.0
R104
R103
R1.0
R1.0
R103
R104
R103