Specifications
General Specifications
Performance Specifications
Item
Specifications
Temperature
Operating
0
°
C to +55
°
C (32
°
F to 131
°
F)
Storage -25
°
C to +70
°
C (-13
°
F to 158
°
F)
Humidity
Operating
30 to 85% RH (Non-condensing)
Storage
30 to 85% RH (Non-condensing)
Withstand voltage
500 V ac for 1 minute between I/O terminal (dc) and frame ground (power unit)
Insulation resistance
100 M
Ω
or more at 500 mega V dc between I/O terminal (dc) and frame ground
(power unit)
Vibration immunity
10 to 55Hz, 1 cycle/minute: double amplitude of 0.75 mm, 10 minutes on 3 axis
(X,Y, Z)
Shock immunity
Peak acceleration and duration 15g/11 ms, 3 times in each X, Y, Z direction
Noise immunity
1500 Vp-p with 50ns to 1
µ
s pulse width (generated by noise simulator)
Ambience
No corrosive gas, no excessive dust
Occupied I/O points
32 points (16 points input, 16 points output)
Max. number of unit
Unlimited
Item
Specifications
Interface
RS232C/RS485 2 ports
Transmission speed
Configured with DSW1 and DSW2
1) Using RS232C: 300/600/1200/4800/9600/19200/38400bps
2) Using RS485: 4800/9600/19200/38400bps
Communication method
Half duplex
Synchronization method
Start-stop method
Transmission distance
Using RS232C: 15m (MAX), Using RS485: 1.2 Km
Transmission code
ASCII or HEX (Binary)
Transmission data
format
STOP bit 1bit/2bit
Parity (even/odd)
Data length 7bit/8bit
Data transmission order
From bit 0, by each character
Transmission unit
A message, to the end code (length adjustable)
Max. message length
MAX. 500 Byte/frame (including end and start codes)
Interface with
CPU unit
Shared memory type:
N-series: Read and write data with advanced instructions F150 (READ) and F151
(WRITE).
Read and write data with advanced instructions READ and WRITE.
I/O allocation
16 points input and 16 points output allocated.
End code setting
Select from three types of
c
cr
d
cr+LF
e
ETX or set arbitrary code from shared
memory.
Start code
Start code
Other special controls
End code cut transmission mode (control by sequence instruction),
Convenient for printing out.
Soft reset (control by sequence instruction)
SCU module is configured as 32 points I/O module with 16 points input and 16 points output.
(For N-series, I/O is allocated by WinFPST S/W and registered as 16SX and 16SY.)
NOTE