Technical Specifications
A-1
A
PPENDIX
A
Technical Specifications
Table A.1 – Service Conditions
AC Line Distribution Capacity
(Maximum)
100KVA, single-phase 115VAC and three-phase 230VAC, with 5,000 amps
symmetrical fault current capacity for M/N 1SU1xxxx and1SU2xxxx drives
1000KVA, three-phase 460 and 575VAC, with 30,000amps symmetrical fault
current capacity for M/N 1SU4xxxx and 1SU5xxxx drives
Control Method
All-digital, pulse-width-modulated (PWM)
Carrier Frequency
4 kHz, 6 kHz, or 8 kHz, software selectable
Displacement Power Factor
0.96
Line Frequency
50/60 Hz (± 5 Hz)
Line Voltage Variation
–10% to +10%
Line Dip RideThrough
500 milliseconds
Linearity
0.05 (Speed reference to output frequency)
Long-term Frequency Stability 0.01%
Minimum Frequency Range
0.5 – 30 Hz
Maximum Frequency Range
30 – 240 Hz
Maximum Load
150% for 1 minute (nominal, based on drive nameplate rating)
Motor Lead Lengths
76 meters (250 feet) total (See table 3.7 for more information)
Overcurrent Trip IET
200% rated drive current
Table A.2 – Dimensions
Enclosure
Height
Depth
Width
Weight
A
304.8mm (12.00”)
121.9mm (4.80”)
146.0mm (5.75”)
2.7 kg (6 lb)
B
301.7mm (11.88”)
160.1mm (6.30”)
222.3mm (8.75”)
5.4 kg (12 lb)
C
357.8mm (14.10”)
158.2 mm (6.20”)
278.1mm (10.9”)
8.1 kg (18 lb)
D
465.2mm (18.31”)
198.9mm (7.83”)
286.5mm (11.28”)
15.3 kg (34 lb)
Table A.3 – Environmental Conditions
Operating Temperature
0° to +40°C (32° to 104°F) – enclosed drives
0° to +55°C (32° to 131°F) – open chassis (cover removed)
Storage Temperature
– 40° to +65°C (– 40° to +149°F)
Humidity
5 to 95% (non-condensing)
Altitude
Do not install the drive above 1000 meters (3300 feet) without derating
output power. For every 91.4 meters (300 feet) above 1000 meters
(3300 feet) up to 3033 meters (10,000 feet), derate the output current by
1%. Above 3033 meters (10,000 feet), contact your local Reliance
Electric sales office for assistance.
Summary of Contents for Reliance SP500
Page 1: ...Instruction Manual SP500 AC Drive Installation and Operation Manual Version 3 1 D2 3356 5 ...
Page 6: ...IV SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 8: ...VI SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 10: ...1 2 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 13: ...Learning About the SP500 Drive 2 3 Figure 2 1 SP500 System Diagram ...
Page 15: ...Learning About the SP500 Drive 2 5 Figure 2 3 Regulator Board Component Locations ...
Page 24: ...2 14 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 27: ...SP500 System Planning 3 3 Figure 3 3 Enclosure C Dimensions Figure 3 4 Enclosure D Dimensions ...
Page 37: ...Installing the Drive 4 3 Figure 4 2 Enclosure B Wire Routing Locations ...
Page 39: ...Installing the Drive 4 5 Figure 4 4 Enclosure D Wire Routing Locations ...
Page 44: ...4 10 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 56: ...5 12 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 60: ...6 4 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 68: ...7 8 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 86: ...8 18 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 110: ...E 8 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 118: ...Index 4 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 120: ......
Page 121: ......