3-6
SP500 AC Drive Installation and Operation Manual Version 3.1
3.2.3 Recommended Control and Signal Wire Sizes
Table 3.6 shows the recommended wire sizes to connect I/O signals to the terminal
strip on the Regulator board. The minimum wire insulation rating is 600V. Operator
controls can be up to 303 meters (1000 feet) from the SP500 drive. All signal wires
should be twisted-pair.
3.2.4 Recommended Motor Lead Lengths
The following motor lead lengths are recommended to reduce line disturbances and
noise. See figure 3.5.
•
For applications using one motor, motor lead length should not exceed 76 meters
(250 feet).
•
For applications with multiple motors, total motor lead length should not exceed 76
meters (250 feet).
When total lead length exceeds 76 meters (250 feet), nuisance trips can occur,
caused by capacitive current flow to ground. Note that these capacitively-coupled
currents should be taken into consideration when working in areas where drives are
running. If the motor lead length must exceed these limits, the addition of output line
reactors or other steps must be taken to correct the problem. See tables 3.7 and 3.8.
Note that the motor lead lengths shown in table 3.7 are maximum distances. Your
application may be restricted to a shorter motor lead length due to:
•
the type of wire
•
the placement of the wire (for example, in conduit or a cable tray)
•
the type of line reactor
•
the type of motor
Table 3.6 – Recommended Control and Signal Wire Sizes and Tightening Torque
Drives Terminals
Minimum
Wire Size
Maximum
Wire Size
Maximum
Tightening Torque
All
1–16
20 AWG,
0.5 (mm
2
)
14 AWG,
2 (mm
2
)
0.5 Newton-meters
(4.5 in-lb)
Figure 3.5 – How to Measure Motor Lead Lengths
SP500 Drive
Motor
38m (125’)
38m (125’)
15m (50’)
61m (200’)
61m (200’)
8m (25’)
8m (25’)
76m (250’)
Motor
Motor
Motor
Motor
Motor
Motor
SP500 Drive
SP500 Drive
SP500 Drive
All examples represent 76m (250’) of motor lead length.
Summary of Contents for Reliance SP500
Page 1: ...Instruction Manual SP500 AC Drive Installation and Operation Manual Version 3 1 D2 3356 5 ...
Page 6: ...IV SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 8: ...VI SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 10: ...1 2 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 13: ...Learning About the SP500 Drive 2 3 Figure 2 1 SP500 System Diagram ...
Page 15: ...Learning About the SP500 Drive 2 5 Figure 2 3 Regulator Board Component Locations ...
Page 24: ...2 14 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 27: ...SP500 System Planning 3 3 Figure 3 3 Enclosure C Dimensions Figure 3 4 Enclosure D Dimensions ...
Page 37: ...Installing the Drive 4 3 Figure 4 2 Enclosure B Wire Routing Locations ...
Page 39: ...Installing the Drive 4 5 Figure 4 4 Enclosure D Wire Routing Locations ...
Page 44: ...4 10 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 56: ...5 12 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 60: ...6 4 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 68: ...7 8 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 86: ...8 18 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 110: ...E 8 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 118: ...Index 4 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 120: ......
Page 121: ......