![Rockwell Automation Reliance SP500 Installation And Operation Manual Download Page 18](http://html.mh-extra.com/html/rockwell-automation/reliance-sp500/reliance-sp500_installation-and-operation-manual_1475455018.webp)
2-8
SP500 AC Drive Installation and Operation Manual Version 3.1
Table 2.2 - Power and NEMA Enclosure Ratings (Continued)
*
To properly size the drive for motor nameplate horsepower and amps, refer to section 3.5 for more information. Derating for 4, 6, 8kHz
carrier frequencies is not required except for the units indicated.
**
Refer to section 2.3.2 for more information on enclosure sizes.
*** Full-load at all carrier frequencies. Refer to section 3.1.3 for more information.
2.3.2 Enclosure Ratings and Sizes
Each of the SP500 drives have one of the following NEMA ratings:
See table 2.2 for a listing of drive model numbers and their individual NEMA ratings.
For clarity in this manual, SP500 drive enclosures are identified by size as enclosures
A through D. Refer to table 2.2 for a listing of the drive model numbers and their
individual enclosure sizes. Refer to section 3.1.1 for the dimensions of enclosures A
through D.
2.4
Component Locations
Figures 2.5 through 2.8 show the main components of the SP500 drives (enclosures A
through D). Appendix F lists replacement parts.
Model
Number
Input Power
and Horsepower
Rating*
NEMA
Rating
Enclosure
Size**
AC Input
Volts
Input
Amps
Input
KVA
Output
Amps*
Power
Loss
Watts***
1SU51002
Three-Phase - 2 HP
1
B
575
3.4
3.3
2.7
90
1SU54002
Three-Phase - 2 HP
4X/12
B
575
3.4
3.3
2.7
90
1SU51003
Three-Phase - 3 HP
1
B
575
5.2
5.1
4.3
120
1SU54003
Three-Phase - 3 HP
4X/12
B
575
5.2
5.1
4.3
120
1SU51005
Three-Phase - 5 HP
1
B
575
7.5
7.5
6.2
150
1SU54005
Three-Phase - 5 HP
4X/12
B
575
7.5
7.5
6.2
150
1SU51007
Three-Phase - 7.5 HP
1
C
575
10.9
10.9
9.0
180
1SU54007
Three-Phase - 7.5 HP
4X/12
C
575
10.9
10.9
9.0
180
1SU51010
Three-Phase - 10 HP
1
C
575
14.5
14.4
12.0
250
1SU54010
Three-Phase - 10 HP
4X/12
C
575
14.5
14.4
12.0
250
NEMA
Rating
Description
1
Vented. For general-purpose indoor applications.
4X/12
Not vented. Supplied with base and keypad gaskets. For use in indoor
environments that require a water-tight and dust-tight enclosure. An
enclosure with this NEMA rating encompasses both ratings (4X and 12).
12
Intended for use in indoor environments that require a dust-tight and
drip-tight enclosure.
Summary of Contents for Reliance SP500
Page 1: ...Instruction Manual SP500 AC Drive Installation and Operation Manual Version 3 1 D2 3356 5 ...
Page 6: ...IV SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 8: ...VI SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 10: ...1 2 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 13: ...Learning About the SP500 Drive 2 3 Figure 2 1 SP500 System Diagram ...
Page 15: ...Learning About the SP500 Drive 2 5 Figure 2 3 Regulator Board Component Locations ...
Page 24: ...2 14 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 27: ...SP500 System Planning 3 3 Figure 3 3 Enclosure C Dimensions Figure 3 4 Enclosure D Dimensions ...
Page 37: ...Installing the Drive 4 3 Figure 4 2 Enclosure B Wire Routing Locations ...
Page 39: ...Installing the Drive 4 5 Figure 4 4 Enclosure D Wire Routing Locations ...
Page 44: ...4 10 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 56: ...5 12 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 60: ...6 4 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 68: ...7 8 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 86: ...8 18 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 110: ...E 8 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 118: ...Index 4 SP500 AC Drive Installation and Operation Manual Version 3 1 ...
Page 120: ......
Page 121: ......