MSR300 Safety System Manual
Rockwell Automation
MSR300 Manual.doc
Pg 74 of 85
Low Byte:
Bit Function
7 Reserved
6
Fault: Different switch settings of input modules between the two channels
5
Fault: Invalid configuration of extension modules
4
Fault: Reserve Muting lamp 2
3
Fault: Muting lamp 2
2
Fault: Reserve Muting lamp 1
1
Fault: Muting lamp 1
0
Fault: at least one Input (lock-out-release, no synchrony activity)
Configuration status (Parameters 4 ... 13: current configuration of Extension
modules 1...10)
High Byte:
Bit Function
7
Switch settings of function bit 3
6
Switch settings of function bit 2
5
Switch settings of function bit 1
4
Switch settings of function bit 0
3
Switch settings of group bit 3
2
Switch settings of group bit 2
1
Switch settings of group bit 1
0
Switch settings of group bit 0
Low Byte:
Bit Function
7
Stored EEPROM settings of function bit 3
6
Stored EEPROM settings of function bit 2
5
Stored EEPROM settings of function bit 1
4
Stored EEPROM settings of function bit 0
3
Stored EEPROM settings of group bit 3
2
Stored EEPROM settings of group bit 2
1
Stored EEPROM settings of group bit 1
0
Stored EEPROM settings of group bit 0
Configuration status (Parameter 14: input with error monitoring)
High Byte:
Bit Function
7
Input error monitoring, extension module 8, input 2
6
Input error monitoring, extension module 8, input 1
5
Input error monitoring, extension module 7, input 2
4
Input error monitoring, extension module 7, input 1
3
Input error monitoring, extension module 6, input 2
2
Input error monitoring, extension module 6, input 1
1
Input error monitoring, extension module 5, input 2
0
Input error monitoring, extension module 5, input 1