The instance value corresponds to the input/output EtherNet/IP target
assemblies in the SmartGuard controller. Enter the Instance number
based on this table.
Instance Number
Connection Type
100 EtherNet/IP Input 1 in
SmartGuard Controller
Input
SmartGuard to MicroLogix Controller
101 EtherNet/IP Input 2 in
SmartGuard Controller
Input
SmartGuard to MicroLogix Controller
103 EtherNet/IP Output 1 in
SmartGuard Controller
Output MicroLogix to SmartGuard Controller
104 EtherNet/IP Output 2 in
SmartGuard Controller
Output MicroLogix to SmartGuard Controller
Configure the message size (in bytes) to match the target assembly
size in the SmartGuard controller.
9.
Click the MultiHop tab.
10.
Configure the routing to target the IP address of the SmartGuard 600
controller.
11.
Click OK.
12.
Verify your changes to the project.
13.
Download the project to the MicroLogix controller.
14.
Place the MicroLogix controller in Run mode.
15.
The status information from the SmartGuard controller now
populates the N7 file of the MicroLogix controller.