Rockwell Automation Publication 20Y-TG002C-EN-P - April 2017
15
Troubleshooting and Error Codes
Chapter 1
100
Param Chksum
The checksum read from the control
board does not match the checksum
that is calculated.
Restore the AFE to the default
configurations.
Cycle the power.
Replace the control board in the power
structure. See
.
104
PwrBrd Chksum
The checksum read from the EEPROM
does not match the checksum that is
calculated from the EEPROM data.
Cycle the power.
Check the fiber optics between the fiber-
optic adapter board and the ASIC board.
See
for
connections.
Replace the fiber-optic adapter board (see
) and/or the ASIC board (see
) in the converter unit.
Contact technical support.
106
MCB-PB Config
The AFE rating information that is
stored on the power board is
incompatible with the control board.
Reset the fault
Cycle the power.
Replace the control board on the power
structure. See
.
Contact technical support.
107
New IO Option
A new option board was added to the
control board.
Clear the fault and verify the correct
parameters for the new option board.
Reprogram parameters as necessary.
113
Fatal App
A Fatal Application error has occurred.
Cycle the power.
Replace the control board on the power
structure. See
.
120
I/O Change
An option board has been replaced.
Reset the fault.
121
I/O Comm Loss
A defective option board or I/O board
slot.
Check the control board-to-I/O option
board connection.
Verify the ground integrity from the
control board to the option board.
Replace the control board and/or I/O
board. See
.
125
LCL OverTemp
The LCL filter has been overheated or
the signal is not connected to input.
Check the LCL filter and signal connection
or verify that digital input 5 is closed. See
.
No. Name
Description
Action (if appropriate)