46
Rockwell Automation Publication 20Y-TG002C-EN-P - April 2017
Chapter 4
AFE Power Structure Component Section
Remove the AFE Airflow Plate
You must remove the airflow plate to remove the power structure from the
AFE.
To remove the AFE airflow plate, follow these steps.
1. Remove power from the AFE.
Remove Power from the AFE on page 37
.
2. If present, remove the protective barriers.
Remove AFE Protective Barriers on page 44
.
3. For an AFE in an IP20 2500 MCC Style enclosure, remove the four M6
x 16 screws that secure the airflow plate to the AFE, and remove the two
M6 x 16 screws that secure the airflow plate to the LCL filter.
For an AFE in an IP21 Rittal enclosure, remove the four T8 Torx-head
screws that secure the airflow plate to the AFE.
4. Slide the airflow plate from the AFE.
Install the AFE Airflow Plate
Install the airflow plate in reverse order of removal.
Remove
Screws
Remove
Screws
Removing Airflow Plate for AFE in
IP21 Rittal Enclosure
Removing Airflow Plate for AFE in IP20
2500 MCC Style Enclosure
Remove
Screws