Rockwell Automation Publication 20Y-TG002C-EN-P - April 2017
69
AFE Power Structure Component Section
Chapter 4
For the procedure to remove the common mode capacitors, see the
PowerFlex Active Front End User Manual, publication
.
See Chapter 2, section ‘Disconnect Common Mode Capacitors’, and
subsection ‘Frame 13 Power Structure’. These instructions apply to an
AFE in an IP20 2500MCC Style enclosure or an AFE in an IP21 Rittal
enclosure.
3. To remove the power supply voltage feedback board from the new
Frame 13 power structure that is replacing the old power structure,
follow the steps.
a. Disconnect the DC bus connection cable from connector J2, and the
motor feedback connection cable from connector J1 at the top of the
power supply voltage feedback board.
b. Carefully disconnect the fiber-optic cables from sockets J4 and J5 on
the side of the power supply voltage feedback board.
c. Secure the cables to the adjacent fan housing so that they are out of
the way.
d. Remove the four screws that secure the power supply voltage
feedback board and cover to the V phase assembly module fan
housing.
e. Carefully remove the power supply voltage feedback board and cover.
f. Disconnect the cable from connector J8 on the power supply voltage
feedback board.
Disconnect:
J2
J1
J4
J5
J8 (located
behind cover)
ATTENTION:
Hazard of permanent eye damage exists when using
optical transmission equipment. This product emits intense light and
invisible radiation. Do not look into fiber-optic ports or fiber-optic
cable connectors.