Rockwell Automation Publication 20Y-TG002C-EN-P - April 2017
123
Appendix
C
Connector Descriptions
Circuit Board Connections
The following tables detail the connection points for the Frame 13 PowerFlex®
Active Front End circuit boards and components.
Table 9 - Fiber-optic Adapter Board-to-ASIC Circuit Board Connections
Fiber-optic Adapter
Connector
Type
Signal Description:
Reference to ASIC Board
Type
ASIC Board Fiber
Connector
(1)
(1) See
for ASIC board Fiber-optic connectors.
H1
TX
Gate_Enable
RX
H1
H2
TX
U_Gate
RX
H2
H3
TX
V_Gate
RX
H3
H4
TX
W_Gate
RX
H4
H5
TX
A/D Convert
RX
H5
H6
TX
VBUS_RX
RX
H6
H7
RX
VBUS_TX
TX
H7
X2
From
+24V DC Power
To
X10
X3
From
Auxiliary 24V DC Power Supply
To
T10 power supply on control
panel
ATTENTION:
Hazard of permanent eye damage exists when using optical
transmission equipment. This product emits intense light and invisible
radiation. Do not look into fiber-optic ports or fiber-optic cable connectors.
IMPORTANT
When mishandled, the ability of fiber-optic cables to transmit data is greatly
diminished.
IMPORTANT
The minimum inside bend radius for fiber-optic cable is 25.4 mm (1 in.).
Any bends with a shorter inside radius can permanently damage the fiber-
optic cable. Signal attenuation increases with decreased inside bend radii.