Chapter 3
Power, Ground, and Wire
Fault Reset Input
The X2/X3 connection can reset some external faults. The reset can occur
automatically or manually. The MSR55P safety relay is shipped from the
factory with a jumper from X2 and X3 for automatic reset. A voltage-free
contact can be used to reset a fault condition manually.
If control of terminal X3 must be by a push button or by a PLC via an
interposing relay, the push button or relay must have the necessary insulation
between the motor voltage and PLC potential.
connections to the fault reset input.
Figure 13 - Fault Reset Circuit Examples
ATTENTION:
Terminals X1-X2-X3 have electrical connections to measuring
inputs L1-L2-L3. Voltage-free contacts that are rated for L1-L2-L3 voltage
must be used for these connections.