Publication 1756-UM001A-EN-P - September 2000
2-8
Communicate with Another Controller over an Ethernet
™
Network
Step 4: Configure the
Message
A.
In the MSG instruction, click
.
B.
Select a configuration for the message:
...
Table 2.A Message to a ControlLogix or FlexLogix controller
If you want to:
For this item:
Type or select:
read (receive) the data
Message Type
CIP Data Table Read
Source Element
first element of the tag that contains data in the other controller
Number Of Elements
number of elements to transfer
Destination Tag
first element of the tag (controller-scoped) in this controller for the data
write (send) the data
Message Type
CIP Data Table Write
Source Tag
first element of the tag (controller-scoped) in this controller that
contains the data
Number Of Elements
number of elements to transfer
Destination Element
first element of the tag for the data in the other controller
Table 2.B Message to a SLC 500 controller
If the data is:
And you want to:
For this item:
Type or select:
integer (s)
read (receive) data
Message Type
SLC Typed Read
Source Element
data table address in the SLC 500 controller (e.g., N7:10)
Number Of Elements
number of integers to transfer
Destination Tag
first element of
int_buffer
write (send) data
Message Type
SLC Typed Write
Source Tag
first element of
int_buffer
Number Of Elements
number of integers to transfer
Destination Element
data table address in the SLC 500 controller (e.g., N7:10)
floating-point (REAL)
read (receive) data
Message Type
SLC Typed Read
Source Element
data table address in the SLC 500 controller (e.g., F8:0)
Number Of Elements
number of values to transfer
Destination Tag
first element of the tag (controller-scoped) in this controller
for the data
write (send) data
Message Type
SLC Typed Write
Source Tag
first element of the tag (controller-scoped) in this controller
that contains the data
Number Of Elements
number of values to transfer
Destination Element
data table address in the SLC 500 controller (e.g., F8:0)
Summary of Contents for Allen-Bradley ControlLogix 1756-L Series
Page 1: ...ControlLogix System 1756 Lx User Manual ...
Page 10: ...Publication 1756 UM001A EN P September 2000 Table of Contents vi ...
Page 64: ...Publication 1756 UM001A EN P September 2000 4 16 Communicate with 1756 I O Notes ...
Page 152: ...Publication 1756 UM001A EN P September 2000 11 4 Monitor Connections Notes ...
Page 160: ...Publication 1756 UM001A EN P September 2000 12 8 Communicate with a DeviceNet Device Notes ...
Page 204: ...Publication 1756 UM001A EN P September 2000 15 16 Communicate Over a Remote I O Network Notes ...
Page 266: ...Publication 1756 UM001A EN P September 2000 21 10 Maintain the Battery Notes ...
Page 286: ...Publication 1756 UM001A EN P September 2000 B 18 Estimate Execution Time Notes ...
Page 300: ...Publication 1756 UM001A EN P September 2000 C 14 Estimate Memory Use Notes ...
Page 305: ......
Page 307: ...ControlLogix System User Manual ...