Publication 1756-UM001A-EN-P - September 2000
6-14
Communicate with 1794 I/O Over a ControlNet
™
Network
Step 6: Validate
Connections
Is this step, you verify that the controller can communicate with the
devices that you have just configured.
Step:
Detailed actions:
A. Determine if communications are
established.
Is a
over the I/O Configuration folder?
If:
Then:
No
The controller can communicate with the module.
Yes
Communications are not established. Go to the next step.
B. Identify a fault. Start at the local
communication module and work
down through the tree.
C. Identify the fault code.
1. Right-click the module and select
Properties
.
2. Click the
Connection
tab.
3. Identify the code for the fault.
!
I/O Configuration
1.
[x] 1756-YYY/x local_com_module
2.
z 17xx-YYY adapter_1
3.
[0] 17xx-YYY module_1
[1] 17xx-YYY module_2
−
!
−
!
−
!
!
!
42437
3.
Summary of Contents for Allen-Bradley ControlLogix 1756-L Series
Page 1: ...ControlLogix System 1756 Lx User Manual ...
Page 10: ...Publication 1756 UM001A EN P September 2000 Table of Contents vi ...
Page 64: ...Publication 1756 UM001A EN P September 2000 4 16 Communicate with 1756 I O Notes ...
Page 152: ...Publication 1756 UM001A EN P September 2000 11 4 Monitor Connections Notes ...
Page 160: ...Publication 1756 UM001A EN P September 2000 12 8 Communicate with a DeviceNet Device Notes ...
Page 204: ...Publication 1756 UM001A EN P September 2000 15 16 Communicate Over a Remote I O Network Notes ...
Page 266: ...Publication 1756 UM001A EN P September 2000 21 10 Maintain the Battery Notes ...
Page 286: ...Publication 1756 UM001A EN P September 2000 B 18 Estimate Execution Time Notes ...
Page 300: ...Publication 1756 UM001A EN P September 2000 C 14 Estimate Memory Use Notes ...
Page 305: ......
Page 307: ...ControlLogix System User Manual ...