Publication 1756-UM001A-EN-P - September 2000
Communicate with Another Controller over an Ethernet
™
Network
2-9
C.
Click the
Communication
tab.
D.
Click
Browse …
E.
Select the 1756-ENET module and click
OK
.
F.
In the
Path
text box, type a comma [ , ].
G.
Type the port number from which the message exits:
Table 2.C Message to a PLC-5 controller
If the data is:
And you want to:
For this item:
Type or select:
integer (s)
read (receive) data
Message Type
PLC5 Typed Read
Source Element
data table address in the PLC-5 controller (e.g., N7:10)
Number Of Elements
number of integers to transfer
Destination Tag
first element of
int_buffer
write (send) data
Message Type
PLC5 Typed Write
Source Tag
first element of
int_buffer
Number Of Elements
number of integers to transfer
Destination Element
data table address in the PLC-5 controller (e.g., N7:10)
floating-point (REAL)
read (receive) data
Message Type
PLC5 Typed Read
Source Element
data table address in the PLC-5 controller (e.g., F8:0)
Number Of Elements
number of values to transfer
Destination Tag
first element of the tag (controller-scoped) in this
controller for the data
write (send) data
Message Type
PLC5 Typed Write
Source Tag
first element of the tag (controller-scoped) in this
controller that contains the data
Number Of Elements
number of values to transfer
Destination Element
data table address in the PLC-5 controller (e.g., F8:0)
For this port:
Specify:
backplane port from a 1756 controller or module
1
DF1 port from a 1756-L1 controller
2
ControlNet port from a 1756-CNB module
Ethernet port from a 1756-ENET module
DH+ port over channel A from a 1756-DHRIO module
DH+ port over channel B from a 1756-DHRIO module
3
Summary of Contents for Allen-Bradley ControlLogix 1756-L Series
Page 1: ...ControlLogix System 1756 Lx User Manual ...
Page 10: ...Publication 1756 UM001A EN P September 2000 Table of Contents vi ...
Page 64: ...Publication 1756 UM001A EN P September 2000 4 16 Communicate with 1756 I O Notes ...
Page 152: ...Publication 1756 UM001A EN P September 2000 11 4 Monitor Connections Notes ...
Page 160: ...Publication 1756 UM001A EN P September 2000 12 8 Communicate with a DeviceNet Device Notes ...
Page 204: ...Publication 1756 UM001A EN P September 2000 15 16 Communicate Over a Remote I O Network Notes ...
Page 266: ...Publication 1756 UM001A EN P September 2000 21 10 Maintain the Battery Notes ...
Page 286: ...Publication 1756 UM001A EN P September 2000 B 18 Estimate Execution Time Notes ...
Page 300: ...Publication 1756 UM001A EN P September 2000 C 14 Estimate Memory Use Notes ...
Page 305: ......
Page 307: ...ControlLogix System User Manual ...