Publication 1756-UM001A-EN-P - September 2000
Communicate with 1756 I/O
4-13
Step 5: Schedule the
ControlNet Network
A.
Download the RSLogix 5000 project to the controller.
B.
Start RSNetworx
™
for ControlNet software.
C.
Has this network been scheduled before?
If:
Then:
No
1. From the
File
menu, select
New
.
2. From the
Network
menu, select
Online
.
3. Select your ControlNet driver (e.g.,
AB_KTC-1
) and click
OK
.
4. Select the
Edits Enabled
check box.
5. From the
Network
menu, select
Properties
.
6. From the
Network Parameters
tab, type or select the following parameters:
In this box:
Specify:
Network Update Time
rate at which the fastest data point on the network must update
Max Scheduled Address
greatest node number to use scheduled communications on the network
Max Unscheduled Address
greatest node number on the network
Media Redundancy
channels in use
Network Name
name for the network
7. Click
OK
.
8. From the
Network
menu, select
Single Pass Browse
.
9. From the
File
menu, select
Save
.
10. Type a name for the file that stores the network configuration, then click
Save
.
11. Select the
Optimize and re-write Schedule for all Connections
button (default) and click
OK
.
12. In RSLogix 5000 software, save the online project.
Yes
1. From the
File
menu, select
Open
.
2. Select the file for the network and click
OK
.
3. From the
Network
menu, select
Online
.
4. Select your ControlNet driver (e.g.,
AB_KTC-1
) and click
OK
.
5. Select the
Edits Enabled
check box.
6. From the
Network
menu, select
Properties
.
7. From the
Network Parameters
tab, update the following parameters:
In this box:
Specify:
Max Scheduled Address
greatest node number to use scheduled communications on the network
Max Unscheduled Address
greatest node number on the network
8. Click
OK
.
9. From the
Network
menu, select
Single Pass Browse
.
10. From the
File
menu, select
Save
.
11. Select the
Optimize and re-write Schedule for all Connections
button (default) and click
OK
.
12. In RSLogix 5000 software, save the online project.
Summary of Contents for Allen-Bradley ControlLogix 1756-L Series
Page 1: ...ControlLogix System 1756 Lx User Manual ...
Page 10: ...Publication 1756 UM001A EN P September 2000 Table of Contents vi ...
Page 64: ...Publication 1756 UM001A EN P September 2000 4 16 Communicate with 1756 I O Notes ...
Page 152: ...Publication 1756 UM001A EN P September 2000 11 4 Monitor Connections Notes ...
Page 160: ...Publication 1756 UM001A EN P September 2000 12 8 Communicate with a DeviceNet Device Notes ...
Page 204: ...Publication 1756 UM001A EN P September 2000 15 16 Communicate Over a Remote I O Network Notes ...
Page 266: ...Publication 1756 UM001A EN P September 2000 21 10 Maintain the Battery Notes ...
Page 286: ...Publication 1756 UM001A EN P September 2000 B 18 Estimate Execution Time Notes ...
Page 300: ...Publication 1756 UM001A EN P September 2000 C 14 Estimate Memory Use Notes ...
Page 305: ......
Page 307: ...ControlLogix System User Manual ...