![Rockwell Automation Allen-Bradley CENTERLINE 2500 Instruction Manual Download Page 38](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-centerline-2500/allen-bradley-centerline-2500_instruction-manual_1475204038.webp)
Publication 2500-IN001A-EN-P - May 2006
4-2
Installing Cable
Lugs
Verify the compatibility of wire size, type and stranding for the power lugs
furnished. Use correct lugs in all applications. Crimp compression lugs with
manufacturer recommended tools.
NOTE:
Use the MCC electrical schematics and wiring diagrams to verify field
wiring connection points.
Incoming Line Lug Compartment
Top or bottom incoming line lug compartments are available. The lug selection
should be based on the size, number and type of conductor.
The following are guidelines for selecting lugs based on incoming line available
short circuit current,
I
cw
.
I
cw
</= 50,000 amperes RMS symmetrical use
mechanical screw
or
crimp/compression
type lugs.
I
cw
> 50,000 amperes RMS symmetrical
crimp
/
compression
type lugs are
recommended.
Main Disconnect Switch
Refer to the documentation package shipped with your MCC for information
on incoming terminations.
For main disconnects, use the lugs provided.
IMPORTANT
Lugs should be installed so they are in line with each other
and proper spacing is used between phases. Hardware must
be tightened per the torque specifications. (See Table 3.1 on
page 14.)
Summary of Contents for Allen-Bradley CENTERLINE 2500
Page 1: ...CENTERLINE 2500 Low Voltage Motor Control Centers Instruction Manual...
Page 3: ...Instruction Manual CENTERLINE 2500 Motor Control Centers...
Page 4: ......
Page 10: ...Publication 2500 IN001A EN P May 2006 iv Notes...
Page 18: ...Publication 2500 IN001A EN P May 2006 1 8 General Information Notes...
Page 22: ...Publication 2500 IN001A EN P May 2006 2 4 Transporting Motor Control Centers Notes...
Page 52: ...Publication 2500 IN001A EN P May 2006 5 12 Commissioning Notes...
Page 82: ...Publication 2500 IN001A EN P May 2006 10 6 Maintenance Notes...
Page 84: ...Publication 2500 IN001A EN P May 2006 11 2 Maintenance After Fault Condition Notes...
Page 86: ...Publication 2500 IN001A EN P May 2006 12 2 Renewal Parts Notes...
Page 87: ......