Chapter 4 Dimensions, Cables, and Wiring
Figure 24 - Kinetix 300 Drives Three-phase (240V) Power Configuration (Delta secondary)
Figure 25 - Kinetix 300 Drives Three-phase (240V) Power Configuration (Delta secondary)
Figure 26 - Kinetix 300 Drives Three-phase (400V) Power Configuration (Wye secondary)
L3
L2
L1
IPD
L3
L2
L1
E
L3
L2
L1
L3
L2
L1
2097-V33PRx
Transformer (Delta) Secondary
Kinetix 300 Drives
Three-phase AC Input
AC Line
(1)
Filter
Bonded Cabinet Ground Bus
Ground Grid or Power Distribution
Ground
M1
Contactor
Input
Fusing
Feeder and branch short-circuit
protection is not illustrated.
(1) Leakage current from the line filter, in this configuration, typically is higher than a balanced (center ground) configuration.
L3
L2
L1
IPD
L3
L2
L1
E
L3
L2
L1
L3
L2
L1
2097-V33PRx
Transformer (Delta) Secondary
Kinetix 300 Drives
Three-phase AC Input
AC Line
(1)
Filter
Bonded Cabinet Ground Bus
Ground Grid or Power Distribution
Ground
M1
Contactor
Input
Fusing
Feeder and branch short-circuit
protection is not illustrated.
(1) Leakage current from the line filter, in this configuration, typically is higher than a balanced (center ground) configuration.
L3
L2
L1
IPD
L3
L2
L1
E
L3
L2
L1
L3
L2
L1
2097-V34PRx
Transformer (Delta) Secondary
Kinetix 300 Drives
Three-phase AC Input
AC Line
(1)
Filter
Bonded Cabinet Ground Bus
Ground Grid or Power Distribution
Ground
M1
Contactor
Input
Fusing
Feeder and branch short-circuit
protection is not illustrated.
(1) Leakage current from the line filter, in this configuration, typically is higher than a balanced (center ground) configuration.