Publication 1794-6.5.12 - September 2011
66
Safety Approvals
North American Hazardous
Location Approval
The 1794-IRT8, 1794-IRT8K, and 1794-IRT8XT modules are North
American Hazardous Location approved.
The following information applies when operating
this equipment in hazardous locations.
Informations sur l’utilisation de cet équipement en
environnements dangereux.
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for
use in Class I Division 2 Groups A, B, C, D, hazardous
locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When combining
products within a system, the most adverse temperature
code (lowest “T” number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne
conviennent qu’à une utilisation en environnements de Classe
I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque
d’identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être
utilisé pour déterminer le code de température global du
système. Les combinaisons d’équipements dans le système
sont sujettes à inspection par les autorités locales qualifiées
au moment de l’installation.
EXPLOSION HAZARD
•Do not disconnect equipment unless
power has been removed or the area is
known to be nonhazardous.
•Do not disconnect connections to this
equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this
equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.
•Substitution of components may
impair suitability for Class I, Division 2.
•If this product contains batteries, they
must only be changed in an area
known to be nonhazardous.
•Couper le courant ou s’assurer que
l’environnement est classé non
dangereux avant de débrancher
l'équipement.
•Couper le courant ou s'assurer que
l’environnement est classé non
dangereux avant de débrancher les
connecteurs. Fixer tous lesconnecteurs
externes reliés à cet équipement à
l'aide de vis, loquets coulissants,
connecteurs filetés ou autres moyens
fournis avec ce produit.
•La substitution de composants peut
rendre cet équipement inadapté à une
utilisation en environnement de Classe
I, Division 2.
•S’assurer que l’environnement est
classé non dangereux avant de changer
les piles.
WARNING
AVERTISSEMENT
Summary of Contents for Allen-Bradley 1794-IRT8K
Page 4: ...Publication 1794 6 5 12 September 2011 iv Summary of Changes Notes ...
Page 8: ...Publication 1794 6 5 12 EN E September 2011 viii Table of Contents Notes ...
Page 62: ...Publication 1794 6 5 12 September 2011 50 Calibrate Your Module Notes ...
Page 84: ...Publication 1794 6 5 12 September 2011 72 Index Notes ...
Page 85: ...Publication 1794 6 5 12 September 2011 Index 73 ...