39
Publication 1794-6.5.12 - September 2011
Chapter
5
Calibrate Your Module
Overview
This chapter provides the tools and equipment, and procedure for calibrating
your FLEX I/OThermocouple, RTD, and mV input module.
When and How to
Calibrate Your FLEX I/O
Module
This module is shipped to you already calibrated. If a calibration check is
required, the module must be in a FLEX system. We recommend recalibrating
your module, if the module is going to be used in an environment with
temperature other than 25 °C (77 °F) and 30% humidity.
Calibration can be accomplished using the manual calibration procedure
described in the following sections.
Topic
Page
When and How to Calibrate Your FLEX I/O Module
Wiring Connections for Calibrating the Thermocouple and RTD
Read and Write Words for Calibration
EDT Calibration Command and Command Data Summary
Channel Loop Compensation Calibration
ATTENTION
Perform module calibration periodically, based on your application, or
at least once a year. Module calibration may also be required to
remove module error caused by aging components in your system.
Offset calibration must be done first, followed by gain calibration.
IMPORTANT
You must use a 1794-TB3G or 1794-TB3GS terminal base when
calibrating this module.
Summary of Contents for Allen-Bradley 1794-IRT8K
Page 4: ...Publication 1794 6 5 12 September 2011 iv Summary of Changes Notes ...
Page 8: ...Publication 1794 6 5 12 EN E September 2011 viii Table of Contents Notes ...
Page 62: ...Publication 1794 6 5 12 September 2011 50 Calibrate Your Module Notes ...
Page 84: ...Publication 1794 6 5 12 September 2011 72 Index Notes ...
Page 85: ...Publication 1794 6 5 12 September 2011 Index 73 ...