Chapter 5
PCCC Commands
92
Rockwell Automation Publication 1756-PM020F-EN-P - January 2019
Request Format: [byte size][file number][file type][element number]
•
[byte size] 1 byte, number of data bytes to be read
•
[file number]1 byte for 0-254; for >=255, 3 bytes, 0xFF followed by 2-byte number, low byte first
•
[file type] 1 byte. For file types and codes, see the
DF1 Protocol and Command Set Reference Manual
Refer to
SLC Communication Command
.
•
[element number] 1 byte, 0-254; 3 bytes for >=255, first byte=0xFF then 2-byte number, low byte first
Reply Format: [data]
[data]
See also
This write command provides a simpler version for writing data.
Request Format: [byte size][file number][file type][element number]
•
[byte size] 1 byte, number of data bytes to be written
•
[file number]1 byte for 0-254; for >=255, 3 bytes, 0xFF followed by 2-byte number, low byte first
•
[file type] 1 byte. For file types and codes, see the
DF1 Protocol and Command Set Reference Manual
Refer to
SLC Communication Command
.
•
[element number] 1 byte, 0-254; 3 bytes for >=255, first byte=0xFF then 2-byte number, low byte first
•
[data]
Reply Format:
no data-only access
See also
SLC Protected Typed Logical
Write with 2 Address Fields
(CMD=0F, 4F; FNC=A9)