CIP services
Chapter 1
Rockwell Automation Publication 1756-PM020F-EN-P - January 2019
23
1st Message Reply Field
Bytes (in hex)
Description - Symbolic Segment Addressing
General Status
06
Reply Data Too Large
Extended Status Size
00
No extended status
Reply Data
C2 00
SINT Tag Type Value
nn nn nn…nn
Data for Elements 0 through 489
2nd Message Request Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Request Service
52
Read Tag Fragmented Service (Request)
Request Path Size
06
Request Path is 6 words (12 bytes) long
Request Path
91 0A 54 6F 74 61 6C 43 6F 75 6E 74
ANSI Ext. Symbolic Segment for
TotalCount
Request Data
D6 06
Number of elements to read (1750)
EA 01 00 00
Start at this byte offset (490) and return as much as will fit
2nd Message Reply Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Reply Service
D2
Read Tag Fragmented Service (Reply)
Reserved
00
General Status
06
Reply Data Too Large
Extended Status Size
00
No extended status
Reply Data
C2 00
SINT Tag Type Value
nn nn nn…nn
Data for Elements 490 through 979
3rd Message Request Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Request Service
52
Read Tag Fragmented Service (Request)
Request Path Size
06
Request Path is 6 words (12 bytes) long
Request Path
91 0A 54 6F 74 61 6C 43 6F 75 6E 74
ANSI Ext. Symbolic Segment for
TotalCount
Request Data
D6 06
Number of elements to read (1750)
D4 03 00 00
Start at this offset (980) and return as much as will fit
3rd Message Reply Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Reply Service
D2
Read Tag Fragmented Service (Reply)
Reserved
00
General Status
06
Reply Data Too Large
Extended Status Size
00
No extended status
Reply Data
C2 00
SINT Tag Type Value