CIP Addressing Examples
Chapter 3
Rockwell Automation Publication 1756-PM020F-EN-P - January 2019
65
Message Reply Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Reply Service
CD
Write Tag Service (Reply)
Reserved
00
General Status
00
Success
Extended Status Size
00
No extended status
See also
Atomic Members of Predefined Data Types
Read two elements of
profile[0,1,257
], which is a three dimensional DINT
array
The values of the tag are 572 and 50988.
Message Request Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Request Service
4C
Read Tag Service (Request)
Request Path Size
09
Request Path is 9 words (18 bytes) long
Request Path
91 07 70 72 6f 66 69 6c 65 00
28 00
28 01
29 00 01 01
ANSI Ext. Symbolic Segment for
profile
Member Segment for 0
Member Segment for 1
Member Segment for 257
Request Data
02 00
Number of elements to read (2)
Message Reply Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Reply Service
CC
Read Tag Service (Reply)
Reserved
00
General Status
00
Success
Extended Status Size
00
No extended status
Reply Data
C4 00
DINT Tag Type Value
F0 02 00 00
2C C7 00 00
0x000002F0 = 752 decimal
0x0000C72C=50988 decimal
See also
Atomic Members of Predefined Data Types
Read one element of
profile[0,1,257]
which is a three dimensional array of
DINTs.
Message Request Field
Bytes (in hex)
Description
Request Service
4C
Read Tag Service (Request)
Request Path Size
07
Request Path is 7 words (14 bytes) long
Example 4 (Symbolic Segment
Addressing Method)
Example 5 (Symbol Instance
Addressing Method)