CIP Addressing Examples
Chapter 3
Rockwell Automation Publication 1756-PM020F-EN-P - January 2019
71
Message Request Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Request Data
01 00
Number of elements to read (1)
Message Reply Field
Bytes (in hex)
Description
Reply Service
CC
Read Tag Service (Reply)
Reserved
00
General Status
00
Success
Extended Status Size
00
No extended status
Reply Data
CA 00
REAL Tag Type Value
33 33 2b 41
0x412B3333=10.7 decimal
See also
Access User-Defined Structures
Read the tag
str1Array[8].travel
which is a one dimensional array of
STRUCT_A.
Message Request Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Request Service
4C
Read Tag Service (Request)
Request Path Size
0B
Request Path is 11 words (22 bytes) long
Request Path
91 09 73 74 72 31 41 72 72 61 79 00
28 08
91 06 74 72 61 76 65 6c
ANSI Ext. Symbolic Segment for
str1Array
,
Member ID for element 8,
ANSI Ext. Symbolic Segment for
travel
Request Data
01 00
Number of elements to read (1)
Message Reply Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Reply Service
CC
Read Tag Service (Reply)
Reserved
00
General Status
00
Success
Extended Status Size
00
No extended status
Reply Data
C4 00
DINT Tag Type Value
0F 27 00 00
0x0000270F=9999 decimal
See also
Access User-Defined Structures
Read two elements of the tag
struct2.hourlyCount[4]
, which is a structure of
type STRUCT_B.
Message Request Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Request Service
4C
Read Tag Service (Request)
Example 3
Example 4